Current Supplied and Consumption Tables on the TM7 Power Bus
The following table gives a synthesis of the current supplied and current consumed on the TM7 power bus by the following TM5 / TM7 System components:
oTM5SBET7 Transmitter module,
oTM7 System expansion blocks (Field bus interface I/O blocks, I/O blocks and Power Distribution Block).
For information on the current supplied to the TM7 power bus, refer to Supplying the TM7 Power Bus.
The following table gives the current supplied and consumed by the expansion blocks on the TM7 System power bus:
Reference |
On the TM7 Power Bus |
||
---|---|---|---|
Current Supplied (mA) |
Current Consumed (mA) |
||
TM7 Field bus interface I/O blocks |
TM7NCOM08B |
150 |
– |
TM7NCOM16B |
750 |
– |
|
TM7NCOM16A |
750 |
– |
|
Digital input |
TM7BDI8B |
– |
38 |
TM7BDI16B |
– |
38 |
|
TM7BDI16A |
– |
38 |
|
Digital output |
TM7BDO8TAB |
– |
38 |
Digital mixed input/output |
TM7BDM8B |
– |
38 |
TM7BDM16A |
– |
38 |
|
TM7BDM16B |
– |
38 |
|
Analog input |
TM7BAI4VLA |
– |
38 |
TM7BAI4CLA |
– |
38 |
|
TM7BAI4TLA |
– |
38 |
|
TM7BAI4PLA |
– |
38 |
|
Analog output |
TM7BAO4VLA |
– |
38 |
TM7BAO4CLA |
– |
38 |
|
Analog mixed input/output |
TM7BAM4VLA |
– |
38 |
TM7BAM4CLA |
– |
38 |
|
(Power Distribution Block) |
TM7SPS1A |
750 |
– |