TM5 Power Distribution Mounting Rules
Installing a PDM according to these rules automatically establishes a new 24 Vdc I/O power segment for I/O expansions to the right of the PDM.
The TM5SPS2• PDM can be placed at the end of the configuration. In this case, it supplies only the TM5 power bus.
Rules:
oDo not mount PDMs side by side
oDo not mount a PDM and a Transmitter or Receiver module side by side
oDo not mount a PDM and an Interface Power Distribution Module (IPDM) side by side
oDo not mount a PDM next to any of the following modules: TM5SAI2H, TM5SAI4H, TM5SAO4L or TM5SAO4H
|
UNINTENDED EQUIPMENT OPERATION |
Do not mount a Power Distribution Module (PDM) next to any one of the following modules: oPower Distribution Module (PDM) oTransmitter module TM5SBET1 or TM5SBET7 oReceiver module TM5SBER2 oInterface Power Distribution Module TM5SPS3 (IPDM) oAnalog input module TM5SAI2H or TM5SAI4H oAnalog output module TM5SAO4L or TM5SAO4H |
Failure to follow these instructions can result in death, serious injury, or equipment damage. |
Installing an SPDM according to these rules automatically establishes a new 24 Vdc I/O power segment for I/O expansions to the right of the SPDM.
Rules:
oDo not mount SPDMs side by side.
oDo not mount an SPDM next to any of the following modules:
oTM5SAI2H
oTM5SAI4H
oTM5SAO4L
oTM5SAO4H
oOnly connect compatible modules to the SPDM.
|
UNINTENDED EQUIPMENT OPERATION |
Do not mount a Safety Power Distribution Module (SPDM) next to any one of the following modules: oAnother Safety Power Distribution Module (SPDM) oAnalog output module TM5SAO4L or TM5SAO4H oAnalog input module TM5SAI2H or TM5SAI4H |
Failure to follow these instructions can result in death, serious injury, or equipment damage. |
Rules:
oDo not mount a PDM next to an IPDM
oDo not mount a Transmitter or Receiver module next to an IPDM
oDo not mount any of the following modules: TM5SAI2H, TM5SAI4H, TM5SAO4L or TM5SAO4H next to an IPDM
|
UNINTENDED EQUIPMENT OPERATION |
Do not mount any one of the following modules next to an Interface Power Distribution Module (IPDM): oPower Distribution Module (PDM) oTransmitter module TM5SBET1 or TM5SBET7 oReceiver module TM5SBER2 oAnalog input module TM5SAI2H or TM5SAI4H oAnalog output module TM5SAO4L or TM5SAO4H |
Failure to follow these instructions can result in death, serious injury, or equipment damage. |