Assembling a Module to a Controller
This section describes how to assemble a module to a controller.
After attaching new I/O modules to the controller, it is important to update and re-download your application program before placing the system back in service. If you do not revise your application program to reflect the addition of new modules, I/O located on the expansion bus may no longer operate normally.
|
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH |
oDisconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment. oAlways use a properly rated voltage sensing device to confirm the power is off where and when indicated. oReplace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit. oUse only the specified voltage when operating this equipment and any associated products. |
Failure to follow these instructions will result in death or serious injury. |
|
UNINTENDED EQUIPMENT OPERATION |
oOnly use software approved by Schneider Electric for use with this equipment. oUpdate your application program every time you change the physical hardware configuration. |
Failure to follow these instructions can result in death, serious injury, or equipment damage. |
Assembling a Module to a Controller
The following procedure shows how to assemble a controller and a module together.
Step |
Action |
---|---|
1 |
Remove all power and dismount any existing controller/IO assembly from its DIN/panel mounting. |
2 |
Remove the expansion connector sticker from the controller or the outermost installed module. |
3 |
Verify that the locking device on the new module is in the upper position. |
4 |
Align the internal bus connector on the left side of the module with the internal bus connector on the right side of the controller or module. |
5 |
Press the new module towards the controller or module until it "clicks" into place. |
6 |
Push down the locking device on the top of the new module to lock it to the controller or previously installed module. |