The factory reset allows you to reset the setting to factory values.
To reset the bus coupler to factory values:
|
Step |
Action |
|---|---|
|
1 |
Remove power from the bus coupler. |
|
2 |
Disconnect all communication cables. |
|
3 |
Set the two rotary switches to position 8 (arrows down). |
|
4 |
Apply power to the bus coupler. |
|
5 |
Wait for a minimum of 30 seconds. |
|
6 |
Set the two rotary switches to position 0 (arrows up). |
|
7 |
Remove power from the bus coupler. |
|
8 |
Apply power to the bus coupler. |