TM3DM8R / TM3DM8RG Characteristics

Introduction

This section describes the general characteristics of the TM3DM8R / TM3DM8RG expansion module.

See also Environmental Characteristics.

Danger_Color.gifDANGER

FIRE HAZARD

oUse only the correct wire sizes for the maximum current capacity of the I/O channels and power supplies.

oFor relay output (2 A) wiring, use conductors of at least 0.5 mm2 (AWG 20) with a temperature rating of at least 80 °C (176 °F).

oFor common conductors of relay output wiring (7 A), or relay output wiring greater than 2 A, use conductors of at least 1.0 mm2 (AWG 16) with a temperature rating of at least 80 °C (176 °F).

Failure to follow these instructions will result in death or serious injury.

Warning_Color.gifWARNING

UNINTENDED EQUIPMENT OPERATION

Do not exceed any of the rated values specified in the environmental and electrical characteristics tables.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Dimensions

The following diagrams show the external dimensions for the TM3DM8R / TM3DM8RG expansion modules:

G-SE-0026826.2.gif-high.gif

 

 

NOTE: * 8.5 mm (0.33 in.) when the clamp is pulled out.

Input Characteristics

The table below describes the inputs characteristics of the TM3DM8R / TM3DM8RG:

Characteristic

Value

Number of input channels

4 inputs

Number of channels groups

1 common line for 4 channels

Input type

Type 1 (IEC/EN 61131-2)

Logic type

Sink/source

Rated input voltage

24 Vdc

Input voltage range

19.2...28.8 Vdc

Rated input current

7 mA

Input impedance

3.4 kΩ

Input limit values

Voltage at state 1

 > 15 Vdc (15..28.8Vdc)

Voltage at state 0

< 5 Vdc (0..5 Vdc)

Current at state 1

> 2.5 mA

Current at state 0

< 1.0 mA

Turn on time

SV(1) < 2.0: 4 ms

SV(1) ≥2.0: 100 μs(2)

Turn off time

Isolation

Between input and internal logic

500 Vac

Between input group and output group

1500 Vac

Between input groups

N/A

Connection type

TM3DM8R

Removable screw terminal block

TM3DM8RG

Removable spring terminal block

Connector insertion/removal durability

Over 100 times

Current draw on 5 Vdc internal bus

24 mA (all inputs and outputs on)

5 mA (all inputs and outputs off)

Current draw on 24 Vdc internal bus

20 mA (all inputs and outputs on)

0 mA (all inputs and outputs off)

(1)   SV refers to the version and is printed on the product label.

(2)   The range depends on the configured filter value. If you use EcoStruxure Machine Expert - Basic, refer to the Modicon TM3 (EcoStruxure Machine Expert - Basic) Expansion Modules Configuration - Programming Guide. If you use EcoStruxure Machine Expert, refer to the Modicon TM3 Expansion Modules - Programming Guide.

Output Characteristics

The table below describes the outputs characteristics of the TM3DM8R / TM3DM8RG:

Characteristic

Value

Number of output channels

4 outputs

Number of channel groups

1 common line for 4 channels

Output type

Relay

Contact type

NO (Normally Open)

Rated output voltage

24 Vdc, 240 Vac

Maximum voltage

30 Vdc, 264 Vac

Minimum switching load

5 Vdc at 10 mA

Rated output current

2 A

Maximum output current

2 A per output

7 A per common

Maximum output frequency

20 operations per minute

Turn on time

Max. 10 ms

Turn off time

Max. 10 ms

Contact resitance

30 mΩ max

Mechanical life

20 million operations

Electrical life

Under resistive load

See Power Limitation

Under inductive load

Protection against short circuit

No

Isolation

Between input and internal logic

500 Vac

Between input group and output group

1500 Vac

Between input groups

N/A

Connection type

TM3DM8R

Removable screw terminal block

TM3DM8RG

Removable spring terminal block

Connector insertion/removal durability

Over 100 times

Current draw on 5 Vdc internal bus

24 mA (all inputs and outputs on)

5 mA (all inputs and outputs off)

Current draw on 24 Vdc internal bus

20 mA (all inputs and outputs on)

0 mA (all inputs and outputs off)

NOTE: Refer to Protecting Outputs from Inductive Load Damage for additional information on this topic.

I/O De-rating

When using TM3DM8R / TM3DM8RG:

G-SE-0026474.1.gif-high.gif

 

    At an ambient temperature of 55 °C (131 °F) in the horizontal mounting direction, limit the inputs and outputs, respectively, which turn on simultaneously as indicated by the X axis.

    At 40 °C (104 °F), all inputs and outputs can be turned on simultaneously at 28.8 Vdc.

Power Limitation

This table describes the power limitation of the TM3DM8R / TM3DM8RG expansion module depending on the voltage, the type of load, and the number of operations required.

These expansion modules do not support capacitive loads.

Warning_Color.gifWARNING

RELAY OUTPUTS WELDED CLOSED

oAlways protect relay outputs from inductive alternating current load damage using an appropriate external protective circuit or device.

oDo not connect relay outputs to capacitive loads.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Power Limitations

Voltage

24 Vdc

120 Vac

240 Vac

Number of operations

Power of resistive loads

AC-12

240 VA

80 VA

480 VA

160 VA

100,000

300,000

Power of inductive loads

AC-15 (cos ϕ = 0.35)

60 VA

18 VA

120 VA

36 VA

100,000

300,000

Power of inductive loads

AC-14 (cos ϕ = 0.7)

120 VA

36 VA

240 VA

72 VA

100,000

300,000

Power of resistive loads

DC-12

48 W

16 W

100,000

300,000

Power of inductive loads

DC-13 L/R = 7 ms

24 W

7.2 W

100,000

300,000