The following illustration shows the location of the USB type A host port of the controller:
NOTE: The USB type A host port provides 500 mA continuous current (USB-standard) and 700 mA for short duration current spikes.
The Modicon M258 Logic Controller allows firmware updates and file transfers using a USB Memory Key. This makes it possible to perform device and data updates without the need for an EcoStruxure Machine Expert instance or the FTP Server.
The USB Host port can be used for upgrading the firmware and data files transfer with a USB Memory key.
For further details on firmware upgrades, please refer to Upgrading Controller Firmware.
For further details on data file transfers, please refer to File Transfer with USB Memory Key.
The following table describes the characteristics for the USB Host port:
|
Characteristic |
Description |
|---|---|
|
Standard |
Hi-speed USB 2.0 Host |
|
Connector type |
A |
|
Maximum baud rate |
480 Mbit/s |
|
Protocol supported |
Mass Storage |
|
Supplied current |
5 Vdc USB Standard |
|
Isolation |
None |
The USB memory key is a standard USB memory key with the following characteristics:
o1 GB minimum capacity
oUSB 2.0 specification or less
oFormatted in FAT16 or FAT32
oA volume label must be set
oSingle partition only
NOTE: Due to the lack of detailed specifications and the variety of typically purchased USB keys, even if a particular key appears to conform to these characteristics, it may still be unrecognized by the controller. Therefore, you should first test any given USB key to assure that it can be recognized by the controller before investing in large quantities of that key.
The following illustration shows the LEDs on the front panel display:
The following table describes the USB status LED:
|
Marking |
Description |
LED |
|
|---|---|---|---|
|
Color |
Description |
||
|
USB Host |
USB Host |
Green / Red |
oOff when nothing is connected oRapid flashing green during exchange oSolid green when no exchange oSolid red for detected script error |