Disassembling a Module from a Controller
This section describes how to disassemble a module from a controller.
|
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH |
oDisconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment. oAlways use a properly rated voltage sensing device to confirm the power is off where and when indicated. oReplace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit. oUse only the specified voltage when operating this equipment and any associated products. |
Failure to follow these instructions will result in death or serious injury. |
Disassembling a Module from a Controller
The following procedure describes how to disassemble a module from a controller.
Step |
Action |
---|---|
1 |
Remove all power from the control system. |
2 |
Dismount the assembled controller and modules from the mounting rail. |
3 |
Push up the locking device from the bottom of the module. |
4 |
Pull apart module from the controller. |