FUNCTION_BLOCK CharCurve_DINT
This function block will evaluate a piecewise linear function (the characteristic curve) at an integral point
. The characteristic curve is specified by a defined number of integral sampling points
InOut:
|
Scope
|
Name
|
Type
|
Comment
|
Input
|
diInputValue
|
DINT
|
interpolation point
|
usiNoPoints
|
USINT
|
number of sampling points defining the characteristic curve ( )
|
Inout
|
ap2diPoints
|
ARRAY [0..10] OF POINT2_DINT
|
array of two dimensional sampling points with
|
Output
|
diOutputValue
|
DINT
|
interpolated value at point
|
xError
|
BOOL
|
error flag
|
wErrorID
|
WORD
|
information on error
0: No error
1: error within array of sampling points (i.e. the sampling points aren't arranged in ascending order)
2: interpolation point diInputValue is outside of area covered by sampling points ( )
4: invalid number of sampling points
|
|