8963 NRT IPAddr not in IPAddressRangeStatic

Description

Refer to Diagnostic class (standard): 2

Cause

Solution

The manually allocated IP address is not within IPAddressRangeStatic.

  • Verify whether a slave with IPConfigMode unequal Automatic IP addressing / 0 is configured and correct if necessary.

  • Verify whether there is an IP address that is not within the calculated IPAddressRangeStatic and correct if necessary.

  • If IPConfigMode = Manual IP addressing (hardware) / 1, verify the IP address that was set on the hardware (for example with a switch) or via the Drives Assistant.

  • If IPConfigMode = Manual IP addressing (software) / 2, verify the IP address that was set in the parameter.