General

Description

6 DI; 6 DI; 6 DO; 4 AI; 2 AO

Compact I/O module 24 Vdc with 2x6 digital inputs, 1x6 digital outputs, 1x4 analog inputs and 1x2 analog outputs

The module consists of the following five submodules:

  • Two submodules with six digital inputs

  • One submodule with six digital outputs

  • One submodule with four analog inputs

  • One submodule with two analog outputs

Configuration Register

Register

Meaning

Default

Data type

Submodule 1

0+0

Digital inputs 1–6

USINT

0+18

Digital input filter

10

USINT

Submodule 2

32+0

Digital inputs 1–6

USINT

32+18

Digital input filter

10

USINT

Submodule 3

64+0

Digital outputs 1–6

USINT

64+20

Delay time error (μs)

ULONG

64+24

Triggering time error (μs)

ULONG

64+30

Status of digital outputs 1–6

USINT

Submodule 4

96+0

Analog input 1

INT

96+2

Analog input 2

INT

96+4

Analog input 3

INT

96+6

Analog input 4

INT

96+16

Analog input filter

0

USINT

96+18

Channel type for analog inputs 1–4

0

USINT

96+20

Lower limit value channel 1–4

-32767

INT

96+22

Upper limit value channel 1–4

32767

INT

96+30

Status of the analog inputs 1–4

USINT

Submodule 5

128+0

Analog output 1

INT

128+2

Analog output 2

INT

128+18

Channel type for analog output

USINT

For further information, see the TM5 compact I/O modules hardware manual.