Type |
AS |
|
Devices supporting the parameter |
Lexium LXM52 Drive, Lexium LXM52 Linear Drive, Lexium LXM62 Power Supply |
|
Traceable |
No |
The parameter is used to display the thermal overload of the braking resistor in percent (0...100 %).
When this parameter reaches the value 90 %, the diagnostic message 8179 Braking resistor load high is triggered.
When this parameter reaches the value 100 %, the braking resistor is deactivated. When more energy recharges the DC bus and no other braking resistor is available to reduce the energy, the voltage of the DC bus rises. When a voltage is too high, the diagnostic messages 8186 DC bus voltage high (LXM62 PS only) or 8108 DC bus overvoltage are triggered. When more than one Lexium LXM62 Power Supply is coupled to one DC bus, the overload of the braking resistors is automatically balanced from V01.54.xx.00 (EcoStruxure Machine Expert V1.0) or higher. When more than one Lexium 52 is coupled to one DC bus, the overload of the braking resistors is automatically balanced from V01.54.xx.00 (EcoStruxure Machine Expert V1.0) or higher. The DC bus coupling of Lexium 62 Power Supplies with Lexium 52 is not allowed.