Symbol:
Function: The dialog is used to assign input actions to specific input events. It also includes specific settings for the selected input action.
Call: In the Input configuration property, click Configure.
Requirement: An element is selected in the editor.
See also
|
Dialogs and actions |
Configures which one of the possible user management dialogs or which action follows the input event Note: The dialog used at runtime is configured in the Dialog Settings tab of the Visualization Manager. See also
Default: Dialogs from the |
|
Login |
The login prompt opens.
Default: |
|
Logout |
The current user is logged out. |
|
Change User Password |
The dialog for changing the password opens.
Default: |
|
Open User Configuration |
The dialog opens for changing the configuration.
Default: |
See also
|
Dialog |
The visualization of type Dialog that will be closed.
Example:
Default dialogs of the
Note: The setting in the object property (Visualization tab) of a visualization determines whether or not a visualization can be used as a dialog. |
|
Result |
Return value for closing the dialog. Note: If there are more input actions after closing, then they configured in the property of the element. |
|
None |
|
|
OK |
|
|
Cancel |
|
|
Abort |
|
|
Retry |
|
|
Ignore |
|
|
Yes |
|
|
No |
See also
|
Dialog |
Visualization (type Dialog). The dialog opens.
Note: The VisuDialogs library provides visualizations (type Dialog).
|
|
Transfer parameters of the dialog |
|
|
Parameter |
Interface parameter as declared in the interface editor of the visualization
Example: |
|
Type |
Data type of the parameter as declared in the interface editor of the visualization.
Example: |
|
Value |
Variable (data type corresponds to the data type of the parameter). The value of the variable is read when the dialog opens and passed to the parameter.
Example:
|
|
Here the return value of the dialog is activated for which the |
|
|
Update |
Note: The parameters are updated before the dialog is closed. Until then, the values are stored temporarily. They are stored as a copy, not as a reference. |
|
None |
|
|
OK |
|
|
Cancel |
|
|
Abort |
|
|
Retry |
|
|
Ignore |
|
|
Yes |
|
|
No |
|
|
Open dialog modal |
|
|
Position to open |
|
|
Centered |
The dialog opens in the center of the visualization. |
|
Position |
The dialog opens at the position defined by X and Y. |
|
X |
Position (in pixels) or variable (integer data type) |
|
Y |
Position (in pixels) or variable (integer data type) |
See also
|
Visualization that is shown at the user input |
|
|
Assign |
Visualization that is selected from all available visualizations in the project or libraries.
Example: |
|
Assign expression |
Variable (
Example: |
|
The order in which visualizations are displayed by user inputs is saved internally. The following options use this information. |
|
|
Previous shown visualization |
Requirement: A visualization switch has already occurred. |
|
Next shown visualization |
Requirement: A visualization switch has already occurred which was called by Previous shown visualization. |
Commands are listed here with transfer parameters that the visualization processes when an input event occurs.
|
Configure commands |
Commands from the list box. Click
|
|
|
The command in Configure commands is added to the list. |
|
|
The command is removed. Requirement: A command is selected. |
|
The order in the list defines the order of execution. |
|
|
|
The selected command is moved down one position in the list. |
|
|
The selected command is moved up one position in the list. |
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
EXE file that is executed on the controller The program is executed on the PLC and therefore it must not be interactive or have any user interfaces. It is possible, for example, for a program to copy a file. |
Program name with directory as |
Arguments of the program as Example: Name of the file that the program opens |
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
EXE file that is executed on the display variant (exception: WebVisu) The program is executed within the context of the display variant. After this, the program may be interactive and have a user interface. |
Program name with directory as |
Arguments of the program as Example: Name of the file that the program opens |
If the visualization is displayed as a CODESYS WebVisu, then no program (EXE file) can be started.
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
The visualization navigates to the web page of the URL. Requirement: The visualization is executed as a CODESYS WebVisu. |
URL
|
If a parameter is not specified, then the web page is displayed in a new window or a new tab.
If |
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
Name of the recipe definition
|
Name of the recipe
|
|
|
At visualization runtime, the controller reads the actual values from the variables of the recipe definition and writes them to the specified recipe. The values are saved implicitly (to a file on the controller) and shown in the recipe definition in the Recipe Manager of CODESYS. In other words, the recipe that is managed in CODESYS is updated with values from the controller. |
||
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
Name of the affected recipe definition
|
Name of the recipe (from the recipe definition)
|
|
|
At visualization runtime, the values of the recipe are written to the variables on the controller as they are in the Recipe Manager. |
||
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
Name of the affected recipe definition
|
Name of the affected recipe that is updated and saved to a file
Optional parameter: If you do not specify a transfer parameter here, then the values from the recipe variables are saved only the file that is specified later. The implicit recipe files are not updated. |
|
|
At visualization runtime, the Save Recipe as dialog opens and prompts the user for a file name and a storage location on the controller. The file name must not be The user can then save the file that includes the actual values from the recipe variables. If a transfer parameter is not specified in the 2nd parameter, then the file is saved without changing an implicit recipe file. If a transfer parameter is given in the 2nd parameter, then the implicit recipe file is also updated. Note: If the Save recipe changes to recipe files automatically option is selected in the Recipe Manager - General tab, then the recipe definition in CODESYS and the implicit recipe files are kept the same automatically.
Note: Implicit (automatically generated) recipe files exist on the controller with names in the following syntax: |
||
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
Name of the affected recipe definition
|
Name of the affected recipe
|
|
|
At visualization runtime, the Load Recipe dialog opens. It provides the visualization user with a file list that is located in the file system of the controller and filters by the extension
Requirement: The file was created with the |
||
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
Name of the affected recipe definition
|
Name of the new recipe
|
|
|
At visualization runtime, a new recipe is created in the given recipe definition. |
||
|
Command |
1st parameter |
2nd parameter |
|
|
|
|
|
Name of the affected recipe definition
|
Name of the recipe
|
|
|
At visualization runtime, the specified recipe is deleted from the recipe definition. |
||
|
Command |
1st parameter |
2nd parameter |
|
|
Optional: File name for the visualization screen to be printed (example: 'Startup image') |
A second parameter cannot be specified for the |
|
The default Printer dialog opens while the visualization is running. In the dialog, you select a printer and configure additional print settings. When you confirm the dialog, the currently displayed visualization screen is printed. Note: The command can be executed in the TargetVisu only. |
||
See also
When the input event occurs, the display switches to another visualization within one frame.
|
Frame selection type |
|
|
Switch local visualization |
The Frame Selection group is visible. |
|
Switch to any visualization |
The Frame and visualization selection group is visible. |
|
Requirement: Switch local visualization is selected. |
|
|
Frame selection |
List of all frames that contain the active visualization. The referenced visualizations are listed below each frame, as determined in the References property of the respective frame. Example:
|
|
Assign selection |
The selection in the Frame selection input field is accepted. Then it appears in the Selected frame and Selected visualization settings. Requirement: A visualization is selected in the Frame selection input field. |
|
Selected Frame |
Name of the frame to be switched to
Example: Hint: Use the Assign selection command for changing the setting here. |
|
Selected Visu |
Name of the switched visualization.
Example: Hint: Use the Assign selection command for changing the setting here. |
|
Requirement: The Switch to any visualization option is selected. |
|
|
Frame and visualization selection |
Contains the frame to be switched to |
|
Assign |
Frame to be switched to (with complete path). The index determines the visualization.
Example:
The path is specified in the following syntax: Caution: Visualizations can be nested at any depth by means of frame elements. In order to use the Switch to any visualization frame selection type without any problems, a frame must not contain more than 21 referenced visualizations. |
|
Assign expression |
Variable (
Example: |
|
Index to select |
Index that determines which of the referenced visualizations is displayed
Note: The referenced visualizations of a frame are indexed automatically according to their order. |
Requirement: The project contains visualizations that form a structure.
See also
The configuration of the input action defines how a visualization user specifies a value and to which variable the value is written.
|
Input type How the input is prompted. |
|
|
Standard |
An input field also opens, or if necessary a virtual keyboard (when the display variant does not have a physical keyboard). Note: The default option for text input at runtime is set in the Visualization Manager: Dialog Settings tab, Settings for Default Text Input. |
|
Text input |
An input field appears. You use the keyboard to specify a number or a text. Requirement: The display variant has a keyboard as input device. |
|
Text input with limits |
An input field appears. You use the keyboard to specify a number or a text. The field also shows the value range for the input. When a limit is passed, the input value is displayed in red. Requirement: The display variant has a keyboard as input device. |
|
VisuDialogs.Keypad |
A virtual keyboard opens. You use it to specify a number or a text. |
|
VisuDialogs.Numpad |
A virtual keyboard opens. You use it to specify a number. |
|
VisuDialogs.NumpadExtended |
A virtual keyboard opens. You use it to specify a number. Hexadecimal and exponential notation are also permitted here. |
|
Choose variable to edit |
|
|
Use text output variable |
|
|
Use another variable |
Example: |
|
Initial display format |
Placeholder with format definition. It defines the output format for the variable value and the input limits.
Example: |
|
Min |
Minimum value of the input limit. If a user specifies a lesser value, then it is not accepted.
|
|
Max |
Maximum value of the input limit. If a user specifies a greater value, then it is not accepted.
|
|
Dialog title |
Text displayed in the title bar of the dialog. Optional.
|
|
Use global setting (from the Visualization Manager) |
|
|
Centered |
|
|
Position |
X, Y: Variable or explicit number (in pixels) for the definition of the upper left corner of the dialog in the coordinate system of the visualization window.
You can use the placeholders |
See also
|
Direction |
From PLC to Visualization From Visualization to PLC |
|
Type |
File Streaming |
|
File name |
Requirement: The transfer type is File.
Name of the file in the file system of the controller. The file name can be specified as a variable of type An absolute or relative path with directory information can also be specified as the file name. Examples:
|
|
Streaming instance name |
Instance name of the object that yields the data for the transfer in streaming mode. The object has to implement the interface Requirement: The transfer type is Streaming. |
|
Control flags |
Variable of type
|
|
Transfer active |
Boolean variable (optional)
|
|
Transfer successful |
Boolean variable (optional)
|
|
Error code |
|
Behavior in online mode (type File)
Transfer from the controller to the visualization (operating panel): The Save File dialog opens. A file name and storage location can be defined on the operating panel for the file that is specified in File name in the input configuration. Then the file is stored there.
Transfer from the visualization (operating panel) to the controller: The Open File dialog opens. Any file can be selected here which is stored as specified in File name on the controller.