The TM5SPS3 Interface Power Distribution Module (IPDM) consists of two dedicated electrical circuits:
oa 24 Vdc main power that serves the electronics of the field bus Interface module and generates independent power for the TM5 power bus that serves the expansion modules.
oa 24 Vdc I/O power segment that serves:
- the expansion modules,
- the sensors and actuators connected to the expansion modules,
- the external devices connected to the Common Distribution Modules (CDM)
The table below provides the main characteristics of the TM5SPS3 :
|
Main Characteristics |
|
|---|---|
|
Maximum current provided on 24 Vdc I/O power segment |
10000 mA |
|
TM5 power bus generated |
750 mA |
The following figure and table provide the references to create a TM5 field bus interface with the TM5SPS3:
|
Number |
Reference |
Description |
Color |
|---|---|---|---|
|
1 |
TM5ACBN1 |
Bus base for field bus interface module and Interface Power Distribution Module |
White |
|
2 |
TM5NS31 |
Sercos Bus Interface module |
White |
|
TM5NCO1 |
White |
||
|
TM5NEIP1 |
White |
||
|
3 |
TM5SPS3 |
Grey |
|
|
4 |
TM5ACTB12PS |
Grey |
NOTE: For more information, refer to TM5 Bus Bases and Terminal Blocks.
The following figure and table provide the TM5SPS3 IPDM status LEDs:
|
LED |
Color |
Status |
Description |
|---|---|---|---|
|
r |
Green |
Off |
Power supply not connected |
|
Single flash |
Reset status |
||
|
Flashing |
TM5 expansion bus in preoperational status |
||
|
On |
RUN status |
||
|
e |
Red |
Off |
OK or module not connected |
|
Double flash |
Indicates one of the following conditions: o24 Vdc I/O power segment, via the external power supply or supplies, is too low. oTM5 power bus, via the external power supply or supplies, is too low. |
||
|
e+r |
Steady red/single green flash |
Invalid firmware |
|
|
l |
Red |
Off |
The TM5 interface power distribution module supply is within the acceptable range. |
|
On |
The TM5 interface power distribution module supply is insufficient. |
||