You can save and restore the application and firmware of a scanned device.
This table describes how to back up the configuration:
Step |
Action |
---|---|
1 |
Insert an SD card in the master controller. |
2 |
Click the button menu to make the LED of the target device flash. |
3 |
Click the button under the menu.Result: The backup menu is displayed. |
4 |
Log in (FTP username and password). |
5 |
Click the button.Result: The saved files are stored in the SD Card. |
The
button is displayed if a backup has been performed.This table describes how to restore the configuration:
Step |
Action |
---|---|
1 |
Insert the SD card which contains your saved configurations in the source controller. |
2 |
Click the button under the menu.Result: The restore menu is displayed. |
3 |
Log in (FTP username and password). |
4 |
Select the configuration to restore. |
5 |
Click the button.Result: A message is displayed asking you to reboot the device. |
6 |
Reboot the device and restart the controller. |