If you replace the motor, the absolute position of the encoder is no longer valid.
WARNING | |
---|---|
Step |
Action |
---|---|
1 |
Power off all supply voltages. Verify that no voltages are present. |
2 |
Label all connections and uninstall the product. |
3 |
Note the identification number and the serial number shown on the product nameplate for later identification. |
4 |
Install the new product as per section Installation. |
5 |
Commission the product as per section Commissioning. |