TM5SE1IC01024 Characteristics

Introduction

This is the description characteristics for the TM5SE1IC01024 electronic module. See also Environmental Characteristics.

Warning_Color.gifWARNING

UNINTENDED EQUIPMENT OPERATION

Do not exceed any of the rated values specified in the environmental and electrical characteristics tables.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

General Characteristics

The table below describes the general characteristics of the TM5SE1IC01024 electronic module:

General Characteristics

Rated power supply voltage

          Power supply source

24 Vdc

Connected to the 24 Vdc I/O power segment

Power supply range

20.4...28.8 Vdc

24 Vdc I/O power segment current draw

58 mA

TM5 power bus 5 Vdc current draw

2 mA

Power dissipation

1.41 W max.

Weight

25 g (0.9 oz)

ID code for firmware update

7084 dec.

Input Characteristics

The table below describes the input characteristics of the TM5SE1IC01024 electronic module:

Input Characteristics

Digital input voltage

20.4...28.8 Vdc

Digital input current at 24 Vdc

3.3 mA

Digital input resistance

7.19 KΩ

Digital input switching threshold:

Low

< 5 Vdc

High

> 15 Vdc

Digital input cycle

≤ 2 µs

Digital input connection type

3-line connections

Digital input circuit

Sink

Digital input additional function

Home enable switch

Isolation between channel and TM5 power bus

See note 1.

Isolation between Channel and encoder

No

Encoder Supply

Max 600 mA

Encoder current at 24 Vdc

1.3 mA

Encoder resistance

18.4 KΩ

Encoder input cycle

≤ 2 µs

Encoder supply internal protection

Short-circuit / Over current

Encoder inputs

24 Vdc / asymmetrical

1 The isolation of the electronic module is 500 Vac RMS between the electronics powered by the TM5 bus and those powered by 24 Vdc I/O power segment connected to the module. In practice, the TM5 electronic module is installed in the bus base, and there is a bridge between the TM5 power bus and the 24 Vdc I/O power segment. The two power circuits reference the same functional ground (FE) through specific components designed to reduce effects of electromagnetic interference. These components are rated at 30 Vdc or 60 Vdc. This effectively reduces isolation of the entire system from the 500 Vac RMS.