TM5SDO4TA and TM5SDO8TA

Introduction

The TM5SDO4TA and TM5SDO8TA expansion electronic modules are 24 Vdc Digital Output electronic modules with 4 and 8 outputs respectively.

For further information, refer to the Hardware Guide:

Reference

Refer to

TM5SDO4TA

TM5SDO4TA Electronic Module 4DO 24 Vdc Tr 2 A 3 Wires

TM5SDO8TA

TM5SDO8TA Electronic Module 8DO 24 Vdc Tr 2 A 1 Wire

TM5 Module I/O Mapping Tab

Variables can be defined and named in the TM5 Module I/O Mapping tab. Additional information such as topological addressing is also provided in this tab.

Refer to the following paragraphs:

oOutput Mapping, for the output parameters configuration details.

oStatus Mapping, for the status bits configuration details.

oInput Mapping, for the input parameters configuration details.

For further generic descriptions, refer to TM5 Module I/O Mapping Tab Description.

Output Mapping

This table describes the TM5SDO4TA and TM5SDO8TA output mapping configuration:

Channel

Type

Description

DigitalOutputs

BYTE

Command word of all outputs

 

DigitalOutput00

BOOL

Command bit of output 0

...

...

DigitalOutput07 (1)

Command bit of output 7

(1)   The number of digital outputs bit is equal to the module output number.

For further generic descriptions, refer to I/O Mapping Tab Description.

Status Bit Mapping

This table describes the TM5SDO4TA and TM5SDO8TA status bit mapping configuration:

Channel

Type

Description

ModuleOK

BYTE

State of the compact I/O and electronic modules

DcOk

BOOL

Voltage range:

o0: Invalid

o1: Valid

reserved

BOOL

Reserved.

NetworkOk

BOOL

TM5 bus:

o0: Bus error

o1: OK

I/O Data valid

BOOL

Data validity:

o0: Valid

o1: Invalid

reserved

BOOL

Reserved

reserved

BOOL

Reserved

reserved

BOOL

Reserved

reserved

BOOL

Reserved

Input Mapping

This table describes the TM5SDO4TA and TM5SDO8TA input mapping configuration:

Channel

Type

Description

StatusDigitalOutputs

BYTE

Status word of all inputs

 

StatusDigitalOutput00

BOOL

Status bit associated to each output:

o0: OK

o1: error detected

...

StatusDigitalOutput07 (1)

PowerSupply

BYTE

Status of power supply

 

reserved

BOOL

Not used

reserved

BOOL

Not used

PowerSupply00

BOOL

Power supply status (0 = DC OK)

(1)   The number of digital inputs bit is equal to the module input number.

For further generic descriptions, refer to I/O Mapping Tab Description.