Refer to Diagnostic class (standard): 3
Default reaction |
||
---|---|---|
AD |
AD |
|
- |
- |
The machine encoder can only be used for position control with a synchronous motor in closed-loop control.
Cause |
Solution |
---|---|
The parameter EncoderMode is set to “Machine encoder is only used for position control / 1”. This setting is not permissible for linear motors. |
Use a synchronous motor or set the parameter EncoderMode to a different value. |
The parameter EncoderMode is set to “Machine encoder is only used for position control / 1”. This setting is not permissible for asynchronous motors. |
Use a synchronous motor or set the parameter EncoderMode to a different value. |