Refer to Diagnostic class (standard): 1
Default reaction |
||
---|---|---|
AD |
– |
The configured Sercos cycle time is too short for the system. Therefore a correct function of the multi carrier transport system is not possible.
Cause |
Solution |
---|---|
Excessive number of Sercos devices in the system. Excessive ring delay for the cycle time. |
Increase the Sercos cycle time to the next higher value. |