Type |
EF |
Offline editable |
Yes |
Devices supporting the parameter |
Lexium LXM52 Drive, Lexium LXM52 Linear Drive, Lexium LXM62 Drive, Lexium LXM62 Linear Drive, Lexium ILM62 Drive Module |
Traceable |
Yes |
The reaction in the drive is defined by ControllerEnableStopMode when ControllerEnable is switched off.
ControllerEnableStopMode |
Reaction when switching off ControllerEnable |
---|---|
User-defined stop / 0 |
Reaction BD2 (default): based on the state of the drive, a reference value profile is calculated in the drive according to the ControllerStopDec, ControllerStopJerk, and UserDefinedStopMode parameter. The brake behaves according to the behavior defined by BrakeMode. By default, it engages at a speed of rotation of less than 10 revolutions per minute. The drive becomes torque-free after StopTimeLim + BrakeCouplingTime at the latest. If the speed of rotation exceeds 10 rpm after StopTimeLim (default value: 400 ms), then diagnostic message |
Best possible stop / 1 |
Reaction BD1: drive is stopped with MaxDrivePeakCurrent peak current. MaxDrivePeakCurrent can be influenced via UserDrivePeakCurrent. The brake behaves according to the behavior defined by BrakeMode. By default, it engages at a speed of rotation of less than 10 revolutions per minute. The drive becomes torque-free after StopTimeLim + BrakeCouplingTime at the latest. If the speed of rotation exceeds 10 rpm after StopTimeLim (default value: 400 ms), then diagnostic message |
Coast down / 2 |
Reaction AD: the motor is connected torque-free. The brake behaves according to the behavior defined by BrakeMode. By default, it engages immediately. |
WARNING | |
---|---|