Replacement of the Optional Module

Required Tool for Replacing the Optional Module

Module part

Tool

Module shaft

Cross slot maximum PH1

How to Disassemble the Optional Module

Step

Action

1

Set main switch to OFF position, or otherwise disconnect all power to the system.

2

Prevent main switch from being switched back on.

3

Undo the two M3x6 screws on the module shaft.

4

Withdraw the module from the cartridge.

Result: The module is deinstalled now and the module shaft is empty.

NOTICE
INOPERABLE EQUIPMENT
Do not remove the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.

How to Install the Optional Module

The module is ready-to-use when delivered.

Step

Action

1

Set main switch to OFF position, or otherwise disconnect all power to the system.

2

Prevent main switch from being switched back on.

3

Insert module into open slot.

4

Screw module to module shaft with two M3x6 screws (tightening torque: 0.5 Nm (4.42 lbf in)).

Result: The module is now installed.

NOTICE
INCORRECT INSERTION OF OPTIONAL MODULE
Do not insert the optional module when the controller is under power.
Failure to follow these instructions can result in equipment damage.