8336 EncoderNet Sync. disturbance detected

Description

Refer to Diagnostic class (standard): 2

An error is detected in the encoder network, when synchronizing the controller system clocks.

Ext. diagnosis: No Sync: xxx

Cause

Solution

More than half of the synchronization telegrams (xxx) specified in SlaveCycleErrorLimit have not been received sequentially. If more synchronization telegrams are not received in a row than specified in SlaveCycleErrorLimit, then the diagnostic message 8335 EncoderNet Sync. disturbance detected is triggered.

This can appear for a number of external reasons related to the network such as wiring, network traffic, performance or other related equipment. Verify and correct if necessary any external equipment or wiring disturbing communications.