Refer to Diagnostic class (standard): 3
The interruption of the Sercos bus has not occurred for at least two cycle times. This diagnostic message normally occurs together with other diagnostic messages (8504 Sercos Read cycle overrun, 8507 Sercos Write cycle overrun).
Cause |
Solution |
---|---|
Wiring error (cable separated). |
Verify and correct if necessary the wiring. |
Non-operating Sercos slave. |
Verify the state and condition of the Sercos slave. Reset or replace the device if necessary. |