Wiring Diagram
The following figure shows the wiring diagram for the TM5SPDD12F:
1 Internal electronics
2 24 Vdc I/O power segment integrated into the bus bases
3 Integrated fuse type T slow-blow 6.3 A 250 V exchangeable
NOTE: I/O electronic modules and the field devices connected to them must all reside on the same 24 Vdc I/O power segment. If not, the status LEDs may not function correctly. In addition, there may potentially be more significant consequences such as an explosion and/or fire hazard.
WARNING
|
|
POTENTIAL EXPLOSION OR FIRE
Connect the returns from the devices to the same power source as the 24 Vdc I/O power segment serving the module.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
The following figure shows the wiring diagram for the TM5SPDD12F with a TM5SDI12D:
1 Internal electronics
2 24 Vdc I/O power segment integrated into the bus bases
3 Integrated fuse type T slow-blow 6.3 A 250 V exchangeable
4 1-wire sensor
WARNING
|
|
UNINTENDED EQUIPMENT OPERATION
Do not connect wires to unused terminals and/or terminals indicated as “No Connection (N.C.)”.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|