Device Replacement

How to Replace the Controller

Before beginning the replacement of specific components, read thoroughly the Prerequisites for Replacing Components and Cables.

 DANGER
INOPERABLE SAFETY FUNCTION
Test the proper functioning of the safety functions after every device replacement and every change of the wiring.
Failure to follow these instructions will result in death or serious injury.

Observe the following instructions to replace the controller.

Step

Action

1

In order to maintain compatibility with your application and machine, replace the existing controller with that of the same hardware revision (for example, RS:02 on the logistical nameplate or 02 in the hardware code.

2

Contact your Schneider Electric service representative if the replacement controller is of a different hardware revision.

3

When replacing the controller, in addition to the following instructions, the specifications of the original machine manufacturer must also be observed.

4

Disconnect cables from the controller.

5

Loosen the mounting screws from the top and bottom of the housing brackets.

6

Remove the controller and replace the complete unit.

7

Install the new controller and tighten the mounting screws.

8

Connect the controller according to the circuit diagram of the machine.

9

Following replacement of the controller, proceed as for the initial start-up.

 DANGER
INCORRECT ASSIGNMENT OF CABLES
Verify that the assignment of the cables conforms to their previous connector assignments.
Failure to follow these instructions will result in death or serious injury.
 CAUTION
FALLING HEAVY OBJECT
Do not fully remove the screw connections of the device mounting suspension and prevent the device from falling out and down.
Failure to follow these instructions can result in injury or equipment damage.
NOTICE
IMPROPER REPLACEMENT / COMMISSIONING
Do not open the controller for commissioning or replacement.
Failure to follow these instructions can result in equipment damage.

How to Start-Up

Proceed as follows to start up:

Step

Action

1

Import the user project again using a PC on which EcoStruxure Machine Expert Logic Builder is installed.

Or

Retrieve the CompactFlash card from the controller to be replaced and insert it into the new controller.

2

Ensure that the CompactFlash card is functional.

3

Put the system back in operation.