Type |
AS |
|
Devices supporting the parameter |
Lexium LXM62 Drive, Lexium LXM62 Linear Drive |
|
Traceable |
Yes |
The parameter represents the state of the effective current limitation, i.e., which current limitation has the lowest threshold. The effective current limitation threshold is indicated via the CurrentLimitationTreshold parameter.
|
Value |
Meaning |
|---|---|
|
0 |
No value available |
|
1 |
Current is limited to the drive peak current (see parameters MaxDrivePeakCurrent and UserDrivePeakCurrent). |
|
2 |
Current is limited to the peak current (see DriveStopCurrentLimit parameter). |
|
3 |
Current is limited to the reference current of the drive (see UserCurrentLimit parameter). |
|
4 |
Current is limited dependent on the present acceleration/deceleration (see parameters AccelerationTorqueLimit and DecelerationTorqueLimit). |
|
5 |
Speed dependent current reduction. (See the diagnostic message “8133 Speed-dependent current reduction”.) |