HSC I/O Mapping for TM218LDA•••DRN
The table below shows the availability of the HSC functions according to the inputs and outputs:
Function |
HSC |
||
---|---|---|---|
Type |
Simple |
||
Channel |
0 |
1 |
|
Fast Input |
I0 |
A |
– |
I1 |
– |
A |
|
A Input counting signal |
HSC I/O Mapping for TM218LDA•••PHN
The table below shows the availability of the HSC functions according to the inputs and outputs:
Function |
HSC |
||||||
---|---|---|---|---|---|---|---|
Type |
Main |
Simple(1) |
Main |
Simple(2) |
|||
Channel |
0 |
0 |
1 |
2 |
2 |
3 |
|
Fast Input |
I0 |
A |
A |
– |
– |
– |
– |
I1 |
B(3)(4) |
– |
A |
– |
– |
– |
|
I2 |
– |
– |
– |
A |
A |
– |
|
I3 |
– |
– |
– |
B(3)(4) |
– |
A |
|
Regular Input |
I4 |
Cap(4) |
– |
– |
– |
– |
– |
I5 |
Sync(4) |
– |
– |
– |
– |
– |
|
I6 |
– |
– |
– |
Cap(4) |
– |
– |
|
I7 |
– |
– |
– |
Sync(4) |
– |
– |
|
Fast Output |
Q0 |
HSC0 reflex Output0(4) |
– |
– |
– |
– |
– |
Q1 |
HSC0 reflex Output1(4) |
– |
– |
– |
– |
– |
|
Q2 |
– |
– |
– |
HSC2 reflex Output0(4) |
– |
– |
|
Q3 |
– |
– |
– |
HSC2 reflex Output1(4) |
– |
– |
|
A Input counting signal B Input counting signal or enable depending configuration of HSC block Sync Reset and start counting Cap Capture current position signal |
(1) Channels HSC0 to HSC1 are usable as a Simple HSC only if HSC0 is not used as a Main HSC.
(2) Channels HSC2 to HSC3 are usable as a Simple HSC only if HSC2 is not used as a Main HSC.
(3) A and B functions depend on the configuration of Main HSC mode.
(4) Used or not according to the configuration of Main HSC mode.
HSC I/O Mapping for TM218LDA•••HN
The table below shows the availability of the HSC functions according to the inputs and outputs:
Function |
HSC |
||||||
---|---|---|---|---|---|---|---|
Type |
Main |
Simple(1) |
Main |
Simple(2) |
|||
Channel |
0 |
0 |
1 |
2 |
2 |
3 |
|
Fast Input |
I0 |
A |
A |
– |
– |
– |
– |
I1 |
B(3)(4) |
– |
A |
– |
– |
– |
|
I2 |
– |
– |
– |
A |
A |
– |
|
I3 |
– |
– |
– |
B(3)(4) |
– |
A |
|
Regular Input |
I4 |
Cap(4) |
– |
– |
– |
– |
– |
I5 |
Sync(4) |
– |
– |
– |
– |
– |
|
I6 |
– |
– |
– |
Cap(4) |
– |
– |
|
I7 |
– |
– |
– |
Sync(4) |
– |
– |
|
Regular Output |
Q0 |
HSC0 reflex Output0(4) |
– |
– |
– |
– |
– |
Q1 |
HSC0 reflex Output1(4) |
– |
– |
– |
– |
– |
|
Q2 |
– |
– |
– |
HSC2 reflex Output0(4) |
– |
– |
|
Q3 |
– |
– |
– |
HSC2 reflex Output1(4) |
– |
– |
|
A Input counting signal B Input counting signal or enable depending configuration of HSC block Sync Reset and start counting Cap Capture current position signal |
(1) Channels HSC0 to HSC1 are usable as a Simple HSC only if HSC0 is not used as a Main HSC.
(2) Channels HSC2 to HSC3 are usable as a Simple HSC only if HSC2 is not used as a Main HSC.
(3) A and B functions depend on the configuration of Main HSC mode.
(4) Used or not according to the configuration of Main HSC mode.
HSC I/O Mapping for TM218LDD24DUPHN and TM218LDD40DUPHNB
The table below shows the availability of the HSC functions according to the inputs and outputs:
Function |
HSC |
||||||
---|---|---|---|---|---|---|---|
Type |
Main |
Simple(1) |
Main |
Simple(2) |
|||
Channel |
0 |
0 |
1 |
2 |
2 |
3 |
|
Fast Input |
I0 |
A |
A |
– |
– |
– |
– |
I1 |
B(3)(4) |
– |
A |
– |
– |
– |
|
I2 |
– |
– |
– |
A |
A |
– |
|
I3 |
– |
– |
– |
B(3)(4) |
– |
A |
|
Regular Input |
I4 |
Cap(4) |
– |
– |
– |
– |
– |
I5 |
Sync(4) |
– |
– |
– |
– |
– |
|
I6 |
– |
– |
– |
Cap(4) |
– |
– |
|
I7 |
– |
– |
– |
Sync(4) |
– |
– |
|
Regular Output |
Q4 |
HSC0 reflex Output0(4) |
– |
– |
– |
– |
– |
Q5 |
HSC0 reflex Output1(4) |
– |
– |
– |
– |
– |
|
Q6 |
– |
– |
– |
HSC2 reflex Output0(4) |
– |
– |
|
Q7 |
– |
– |
– |
HSC2 reflex Output1(4) |
– |
– |
|
A Input counting signal B Input counting signal or enable depending configuration of HSC block Sync Reset and start counting Cap Capture current position signal |
(1) Channels HSC0 to HSC1 are usable as a Simple HSC only if HSC0 is not used as a Main HSC.
(2) Channels HSC2 to HSC3 are usable as a Simple HSC only if HSC2 is not used as a Main HSC.
(3) A and B functions depend on the configuration of Main HSC mode.
(4) Used or not according to the configuration of Main HSC mode.