Diagnostics information and status information on the safety module eSM is provided by the drive. Refer to the user guide of the drive (Related Documents) for additional information.
The states of the inputs and the outputs as well as the operating states of the eSM safety modules can be read via the fieldbus. The parameters are accessed in the same way as the parameters of the drive.
The menu item "Status" in the commissioning software allows you to display the status of the safety module eSM.
Problem |
Possible causes |
Remedy |
---|---|---|
Machine operating mode Automatic Mode does not start even though the guard door is closed. |
The acknowledge/reset pushbutton for the guard door is not connected or not activated. |
Connect an acknowledge/reset pushbutton for the guard door to GUARD_ACK or activate a connected acknowledge/reset pushbutton. |
Guard door acknowledgement is not required, but configured. |
Verify correct settings for the eSM parameter MiscModes. |
|
The safety module eSM remains in the eSM operating state 2. |
Supply not connected. |
Connect ESM24VDC and ESM0VDC. |
eSM parameter password forgotten. |
eSM parameter password has been changed or forgotten. |
Duplicate an eSM parameter set from a different safety module eSM with known eSM parameter password. Set the eSM parameters to the required values. |