Refer to Diagnostic class (standard): 2
Default reaction |
||
---|---|---|
D |
E |
|
- |
- |
|
D |
- |
The cooling element of the PacDrive servo amplifier is overheated. An 8101 Power stage overtemperature error may result.
The temperature of the power stage of the multi carrier segment is high.
For the Multi carrier transport system: |
|
---|---|
Cause |
Solution |
The cooling of the multi carrier segments is not sufficient. |
Improve the thermal transition between the multi carrier segments and the mounting plate (for example, by using thermal paste). |