8127 Motor temperature high

Description

Refer to Diagnostic class (standard): 2

  • This diagnostic message is triggered as soon as the motor temperature reaches a value that is 5 degrees below the triggering threshold of diagnostic message 8102 Motor overtemperature.

    The motor temperature is measured either by a temperature sensor or by a thermal model.

    The MotorTemperatureMonitoring parameter is used to determine how the motor temperature is measured.

  • The temperature of the multi carrier segment coils is high.

For the Multi carrier transport system:

Cause

Solution

The load on the multi carrier segment is too high.

Verify your application and reduce the acceleration if necessary.

The cooling of the multi carrier segments is not sufficient.

Improve the thermal transition between the multi carrier segments and the mounting plate (for example, by using thermal paste).