Function for setting a command within a command table that shall be sent to the module after the previous command has been processed.
The function helps to initialize tables easily.
The function writes the value of iq_udiStepIndex to the iq_iStepIndex variable and adds 1. The slave field index of the table is assigned with this variable;
10 is added to the value of iq_diStep in the iq_diStep variable. It is written back in iq_diStep. This is the identification of an additional step for the FB_ModuleController.
Output |
Data type |
Description |
---|---|---|
q_etDiag |
General, library-independent statement on the diagnostic. A value not equal to ET_Diag.Ok corresponds to an error message. |
|
q_etDiagExt |
POU-specific output on the diagnostic. q_etDiag = ET_Diag.Ok -> Status message q_etDiag <> ET_Diag.Ok -> Error message |
Input/Output |
Data type |
Description |
---|---|---|
iq_udiStepIndex |
UDINT |
Input/output for the variable for managing the index within the command table. |
iq_diStep |
DINT |
Input/output for the variable for managing the step number of the command to be entered. |