Type |
EF |
|
Offline editable |
Yes |
|
Devices supporting the parameter |
Lexium LXM52 Drive, Lexium LXM62 Drive |
|
Traceable |
– |
Used to select the motor control mode.
|
Value |
Data type |
Meaning |
|---|---|---|
|
closed-loop control / 0 |
DINT |
The servo amplifier works in closed-loop controlled operation. An encoder is required for the closed-loop controlled operation. |
|
open-loop control / 1 |
DINT |
The servo amplifier works in the open-loop controlled operation. The controller works without an encoder (no feedback). Only asynchronous motors can be used in the open-loop controlled operation. The speed of rotation is not monitored. |
|
encoderless velocity closed-loop control / 2 |
DINT |
The servo amplifier works in the encoderless velocity control operation. The controller works without a position sensor (any kind of encoder). This setting has no effect for the Lexium LXM52 Drive. |
The parameter is only transferred to the drive by a Sercos phase up (phase 0 => phase 4). After modification of the parameter, a new Sercos phase up has to be performed.