The module is an IO-Link master that can be used to connect sensors and actuators (IO-Link devices) to the TM5 system in accordance with the IO-Link standard.
Operation with PacDrive controllers: TM5NS31 bus coupler via Sercos
Operation with M262 Logic/Motion controllers: TM5NS31 bus coupler via Sercos and/or TM5NEIP1 bus coupler via Ethernet/IP
Feature overview TM5SE4IOL:
Four IO-Link devices.
Four digital channels, which can be configured as input or output.
24 Vdc and 0 V for sensor/actuator supply.
The four channels provided by the TM5SE4IOL module can be used as IO-Link channels or, in Standard Input Output (SIO) mode, as standard digital inputs or outputs, depending on the capabilities and configuration of the connected IO-Link devices.
The suitability of an IO-Link device for a given application depends, among other things, on the fieldbus cycle time, the bus task time, the bitrate of the IO-Link device, etc.
The IO-Link master module TM5SE4IOL must be operated with a bus base and a terminal block. Refer to Ordering Information for details.
Third-party sensors and actuators can be connected to the IO-Link master module TM5SE4IOL. You must fully read and understand the documentation of the third-party sensors and actuators to be familiar with the I/O mapping of the sensors and actuators connected to the IO-Link master module TM5SE4IOL. The code you create to control third-party sensors and actuators via the IO-Link module is not verified by EcoStruxure Machine Expert.
| WARNING | |
|---|---|
|
Commercial reference |
Number of channels |
Voltage/current per channel |
Wiring |
Source/sink |
|---|---|---|---|---|
|
TM5SE4IOL |
Up to 4 |
24 Vdc / 4 mA |
3 wires |
Sink |
|
Commercial reference |
Number of channels |
Voltage/current per channel |
Wiring |
Source/sink |
|---|---|---|---|---|
|
TM5SE4IOL |
Up to 4 |
24 Vdc / 0.25 A |
3 wires |
Source |
|
Characteristic |
Value and description |
|---|---|
|
Voltage |
24 Vdc power segment supply minus voltage drop for internal protection |
|
Voltage drop for internal protection at 500 mA |
0.3 Vdc maximum |
|
Current |
2 A |
|
Internal protection |
Overcurrent and short circuit |
|
Overcurrent protection |
|