Refer to Diagnostic class (standard): 3
Default reaction |
||
---|---|---|
AD |
AD |
|
- |
- |
The encoder interface of the motor name plate is not according to the encoder interface identified by the device.
Cause |
Solution |
---|---|
The variable uiEncoderType in the data structure ST_UserMotorData is set to an incorrect value. |
Set the variable to the correct value. |
The wrong encoder is connected to this device. |
Verify and correct if necessary the wiring of the encoder. |
Encoder is inoperable. |
Replace the motor, or the encoder if possible. |