Code |
Description |
Comment |
---|---|---|
0xC10CA100 |
S-0-1508.x.67 Sub-bus tunnel procedure command |
The procedure command S-0-1508.x.67 Sub-bus tunnel procedure command is in process. |
0xC10CA101 |
S-0-1508.x.67: Unsupported Sub-bus Tunnel PDU version |
The requested tunnel version is not supported by the slave. |
0xC10CA102 |
S-0-1508.x.67: Unsupported Sub-bus SDU Type |
The requested Sub-bus SDU type is not supported by the slave. |
0xC10CA103 |
S-0-1508.x.67: Unsupported Sub-bus Tunnel SDU version |
The requested SDU version is not supported by the slave. |
0xC10CA104 |
S-0-1508.x.67: Incorrect sub-bus slave index |
Not supported sub-bus slave index (for example, no physical port available for this index) or sub-bus slave not present. |
0xC10CA105 |
S-0-1508.x.67: Incorrect length of SDU |
Length of SDU differs from LengthOfSDU field (see Sub-bus Tunnel Header). |
0xC10CA106 |
S-0-1508.x.67: Incorrect length of Command SDU |
Length of Command SDU differs from LengthOfCommandSDU field (see Command Header). |
0xC10CA107 |
S-0-1508.x.67: Answer PDU too large |
The answer PDU is too large. The sercos master shall send fewer Command PDUs. |
0xC10CA108 |
S-0-1508.x.67: Buffer overflow |
Overflow of internal buffers/queues. |
0xC10CA120 |
S-0-1508.x.80 Sub-bus reconfiguration procedure command |
The procedure command S-0-1508.x.80 Sub-bus reconfiguration procedure command is in process. |
0xC10CA200 |
S-0-1500.x.21 Local bus reconfiguration procedure command |
The procedure command S-0-1500.x.21 Local bus reconfiguration procedure command is in process. |
0xC10CBC00 |
S-0-1500.x.12 Rearrangement of IO resource procedure command |
The procedure command S-0-1500.x.12 Rearrangement of IO resource procedure command is in process. |
0xC10CBC01 |
S-0-1500.x.12: Invalid/forbidden slot number |
An attempt was made to insert/replace a generic IO function group with an invalid/forbidden slot number. |
0xC10CBC02 |
S-0-1500.x.12: Forbidden insertion/replacement of IO bus coupler |
An attempt was made to insert/replace the function group IO bus coupler (S-0-1500.x.0). |
0xC10CBC03 |
S-0-1500.x.12: Undefined generic IO function group |
An attempt was made to insert/replace an undefined generic IO function group. |
0xC10CBC04 |
S-0-1500.x.12: Duplicate entries |
The list of inserted/replaced function groups (S-0-1500.x.4/11) contains duplicate entries. |
0xC10CBC05 |
S-0-1500.x.12: List is not sorted |
The list of inserted/replaced function groups (S-0-1500.x.4/11) is not sorted in an increasing order (slot number, data block number). |
0xC10CBC0F |
S-0-1500.x.12: Memory error detected |
Not enough memory available. |
Code |
Description |
Comment |
---|---|---|
0xC10FA033 |
Data length configuration error |
At least one of the sub-bus slaves lengths given in IDNs S-0-1508.x.76 List of Connected Sub-bus Slave Output Data Lengths resp. S-0-1508.x.78 List of Connected Sub-bus Slave Input Data Lengths is greater than the configured lengths. |
0xC10FA043 |
Sub-bus is running asynchronous (in relation to the Sercos bus cycle) |
Only in case of a synchronous configured sub-bus in CP4. |
Code |
Description |
Comment |
---|---|---|
0xC10x0000 |
No error |
- |
0xC10x1000 |
General error |
Refer to the manual or contact the support team of the manufacturer of the connected device. |
0xC10x2000 |
Current |
General current error. |
0xC10x2100 |
Current on the device input side |
Error affecting the power supply of the device or signals at the "device input side". |
0xC10x2110 |
Short circuit/ground error |
- |
0xC10x2120 |
Ground error |
Ground error on device supply voltage - general. |
0xC10x2130 |
Short circuit |
Short circuit on device supply voltage - general (for example, 24 V and GND). |
0xC10x2136 |
Short circuit to VCC |
- |
0xC10x2137 |
Short circuit to Ground |
- |
0xC10x2140 |
Short circuit peripheral |
Short circuit / cross-circuit on the peripheral. |
0xC10x2141 |
Cross-circuit output |
Cross-circuit between signal outputs and / or signal outputs and other voltages. |
0xC10x2142 |
Cross-circuit output and a clock signal |
Cross-circuit between a signal output and a clock signal. |
0xC10x2146 |
Short circuit input to VCC |
Short circuit (cross-circuit) of a signal input to VCC. |
0xC10x2147 |
Short circuit input to GND |
Short circuit (cross-circuit) of a signal input to GND. |
0xC10x2150 |
Open signal lines |
Open signal lines (input signal not connected). |
0xC10x2160 |
Signal line break |
Signal line break / cable break (input signal). |
0xC10x2180 |
Input is not activated |
Input is not activated (inoperative). |
0xC10x2181 |
Input circuit |
Input circuit (for example, load) error. |
0xC10x2200 |
Current inside the device |
Error affecting internal power supplies or "internal device" signals. |
0xC10x2213 |
Overcurrent on startup |
- |
0xC10x2214 |
Overcurrent during operation |
- |
0xC10x2220 |
Continuous overcurrent |
Continuous overcurrent from an internal voltage source. |
0xC10x2230 |
Short circuit/ground error |
Short circuit/ground error of an internal voltage source. |
0xC10x2240 |
Ground error |
- |
0xC10x2250 |
Short circuit |
- |
0xC10x2300 |
Current on the device output side |
Error in the power supply or signals for the peripheral connected to the device (device output side). |
0xC10x2310 |
Continuous over current |
Continuous overcurrent on peripheral supply - general. |
0xC10x2320 |
Short circuit/ground error |
Short circuit/ground error in peripheral supply - general. |
0xC10x2330 |
Ground error |
Ground error in peripheral supply voltage. |
0xC10x2340 |
Short circuit |
Short circuit/overload on the peripheral. |
0xC10x2344 |
Output overload |
Overload of a signal output. |
0xC10x2345 |
Sensor supply overload |
Overload of initiator supply. |
0xC10x2346 |
Short circuit to VCC |
Short circuit (cross-circuit) of a signal output to VCC. |
0xC10x2347 |
Short circuit to ground |
Short circuit (cross-circuit) of a signal output to GND. |
0xC10x2350 |
Open circuit |
Continuously open signal lines (output). |
0xC10x2360 |
Wire break |
Signal line break / cable break (output signal). |
0xC10x2370 |
Cross-circuit |
Cross-circuit. |
0xC10x2371 |
Cross-circuit outputs |
Cross-circuit between signal outputs and / or signal outputs and other voltages. |
0xC10x2372 |
Cross-circuit outputs/clock |
Cross-circuit between a signal output and a clock signal. |
0xC10x2380 |
Output is not activated (inoperative) |
- |
0xC10x2381 |
Signal output circuit (for example, load) error |
- |
0xC10x3000 |
Voltage |
- |
0xC10x3100 |
Mains voltage |
Voltage on the device input side -power supply. |
0xC10x3110 |
Mains overvoltage |
- |
0xC10x3120 |
Mains undervoltage |
- |
0xC10x3130 |
Mains error |
- |
0xC10x3134 |
Phase sequence |
- |
0xC10x3140 |
Mains frequency |
- |
0xC10x3141 |
Frequency too high |
- |
0xC10x3142 |
Frequency too low |
- |
0xC10x3150 |
Polarity of supply voltage |
Polarity of supply voltage reversed. |
0xC10x3180 |
Signal input - general |
Error affecting the signal input - general. |
0xC10x3181 |
Open signal line (input) |
- |
0xC10x3182 |
Wire break |
Signal line break / cable break (input signal). |
0xC10x3183 |
Unexpected signal change |
Unexpected signal change at signal input. |
0xC10x3184 |
Overvoltage at signal input |
Voltage greater than the permitted range. |
0xC10x3185 |
Signal voltage within non-defined area |
- |
0xC10x3186 |
Undervoltage at signal input |
Voltage less than the permitted range. |
0xC10x3200 |
Voltage inside the device |
Error affecting internal power supplies or "internal device" signals. |
0xC10x3210 |
Overvoltage inside the device |
- |
0xC10x3220 |
Undervoltage inside the device |
- |
0xC10x3230 |
Charging error |
- |
0xC10x3300 |
Output voltage |
Voltage on the device output side, for example, supply or working voltage for external parts. |
0xC10x3310 |
Output overvoltage |
- |
0xC10x3320 |
Output undervoltage |
- |
0xC10x3400 |
Supply voltage |
Error in the supply voltage for the peripheral. |
0xC10x3401 |
Supply voltage - overvoltage |
Supply voltage for the peripheral - overvoltage. |
0xC10x3402 |
Supply voltage - absent |
Supply voltage for the peripheral - unavailable. |
0xC10x3403 |
Supply voltage - undervoltage |
Supply voltage for the peripheral - undervoltage. |
0xC10x3410 |
Sensor supply - common |
- |
0xC10x3411 |
Sensor supply undervoltage |
- |
0xC10x3412 |
Sensor supply missing |
- |
0xC10x3413 |
Sensor supply overvoltage |
- |
0xC10x3420 |
Actuator supply - common |
- |
0xC10x3421 |
Actuator supply undervoltage |
- |
0xC10x3422 |
Actuator supply missing |
- |
0xC10x3423 |
Actuator supply overvoltage |
- |
0xC10x4000 |
Temperature |
Temperature - not within the permitted range. |
0xC10x4100 |
Ambient temperature |
- |
0xC10x4110 |
Ambient overtemperature |
Excess temperature in the surrounding area. |
0xC10x4120 |
Ambient undertemperature |
Low temperature in the surrounding area. |
0xC10x4130 |
Intake air temperature |
- |
0xC10x4140 |
Exhaust air temperature |
- |
0xC10x4200 |
Device temperature |
- |
0xC10x4210 |
Device overtemperature |
Excess temperature in the device. |
0xC10x4220 |
Device undertemperature |
Insufficient temperature in the device. |
0xC10x4300 |
External temperature (for example, drive) |
Temperature of an external peripheral device (for example, drive) not OK. |
0xC10x4310 |
External overtemperature (for example, drive) |
Excess temperature in the external peripheral device (for example, drive). |
0xC10x4320 |
External undertemperature (for example, drive) |
Insufficient temperature in external peripheral device (for example, drive). |
0xC10x4400 |
Supply temperature |
Temperature of supply unit not OK. |
0xC10x4410 |
Supply overtemperature |
Excess temperature of supply unit. |
0xC10x4420 |
Supply undertemperature |
Insufficient temperature of supply unit. |
0xC10x5000 |
Device hardware (only inside the device housing) |
- |
0xC10x5010 |
Component error |
- |
0xC10x5100 |
Supply |
Error in the supply inside and through the device. |
0xC10x5110 |
Supply low voltage |
For the internal voltages 24 V, 5 V, 3.3 V, 3.0 V, 2.5 V, 1.8 V. |
0xC10x5120 |
Supply for air |
- |
0xC10x5130 |
Supply for paint |
- |
0xC10x5140 |
Supply for intermediate circuit |
- |
0xC10x5150 |
Supply for initiator |
Error of the supply for an external sensor supplied from inside the device. |
0xC10x5151 |
Internal short circuit |
- |
0xC10x5160 |
Supply for peripheral devices |
Error of the supply for external peripherals supplied from inside the device. |
0xC10x5200 |
Control system |
- |
0xC10x5210 |
Measuring circuits |
- |
0xC10x5220 |
Computer circuits |
- |
0xC10x5230 |
Communication (inside the device) |
Communication (internal device only) disrupted. |
0xC10x5300 |
Operating and display unit |
- |
0xC10x5400 |
Power section |
Error in the power section of the device. |
0xC10x5410 |
Output stages |
- |
0xC10x5420 |
Choppers |
- |
0xC10x5430 |
Input stages |
- |
0xC10x5440 |
Contactors |
- |
0xC10x5450 |
Fuses |
- |
0xC10x5500 |
Communication with add-on module |
- |
0xC10x5600 |
Internal memory |
Error in the internal memory. |
0xC10x5610 |
RAM |
Permanently installed RAM error. |
0xC10x5620 |
EPROM |
Permanently installed EPROM error. |
0xC10x5630 |
EEPROM |
Permanently installed EEPROM error. |
0xC10x5640 |
Flash memory |
Permanently installed flash error. |
0xC10x6000 |
Device software |
Device software error. |
0xC10x6010 |
Software reset (watchdog) |
Software reset (watchdog) occurred. |
0xC10x6100 |
Internal software (Flexware) |
Internal software error (Flexware). |
0xC10x6110 |
Flexware missing |
- |
0xC10x6120 |
Flexware inconsistent |
- |
0xC10x6130 |
Application not yet ready |
Application on the device not yet ready (part of application still booting, self-tests being performed, and so on). |
0xC10x6200 |
Application software |
Error in the user software on the device. |
0xC10x6300 |
Data record not OK |
User parameter (data record) not OK. |
0xC10x6310 |
Parameter missing |
Loss of internally stored user parameters. |
0xC10x6320 |
Parameter error |
Inconsistency between internally stored user parameters (for example, identified by CRC). |
0xC10x6330 |
Parameter not yet initialized |
User (start-up) parameters not yet initialized. |
0xC10x6800 |
Configuration |
Device configuration not OK. |
0xC10x6810 |
Process data double mapped |
Data in the process data configuration double mapped. |
0xC10x7000 |
Add-on modules error |
Permanently connected to the device, can be applied by the user, if necessary, part of complete device, usually delivered with device. |
0xC10x7100 |
Power |
Error in the power section. |
0xC10x7140 |
Replaceable relay / contactor |
Replaceable relay / contactor (by the user) error. |
0xC10x7150 |
Replaceable fuse |
Replaceable fuse (by the user) error. |
0xC10x7200 |
Measuring circuit |
- |
0xC10x7300 |
Sensor |
Error in the sensor (component connected permanently with the device). |
0xC10x7400 |
Computer circuit |
Error in the calculation circuit. |
0xC10x7500 |
Communication |
Disruption in communication with additional assembly. |
0xC10x7600 |
Data memory |
Error in external memory. |
0xC10x7610 |
RAM |
Replaceable RAM error. |
0xC10x7620 |
EPROM |
Replaceable EPROM error. |
0xC10x7630 |
EEPROM |
Replaceable EEPROM error. |
0xC10x7640 |
Flash memory |
Replaceable flash error. |
0xC10x7700 |
Open circuit cable error |
- |
0xC10x7710 |
Open circuit at sensor cable |
- |
0xC10x8000 |
Monitoring |
Monitoring of device function. |
0xC10x8100 |
Communication |
Disruption in fieldbus communication. |
0xC10x8110 |
Process data monitoring |
Process data update timeout expired. |
0xC10x8120 |
Host monitoring |
Host data update timeout expired. |
0xC10x8121 |
Process data channel handshake timeout expired |
- |
0xC10x8150 |
Buffer handling error |
- |
0xC10x8151 |
Transmitting buffer, general |
- |
0xC10x8152 |
Transmitting buffer full |
- |
0xC10x8153 |
Transmitting buffer overflowed |
- |
0xC10x8159 |
Receiving buffer, general |
- |
0xC10x815A |
Receiving buffer full |
- |
0xC10x815B |
Receiving buffer overflowed |
- |
0xC10x8200 |
Closed-loop control |
- |
0xC10x8210 |
System deviation high |
The expected, manufacturer specific - deviation present longer than a specified period of time. |
0xC10x8211 |
Maximum manipulated variable reached |
- |
0xC10x8220 |
System deviation |
The expected, manufacturer specific - deviation present longer than a specified time. |
0xC10x8221 |
Minimum manipulated variable reached |
- |
0xC10x8900 |
Sensors |
Error on external sensor (separate device). |
0xC10x8910 |
Measured value overrange |
- |
0xC10x8920 |
Measured value underrange |
- |
0xC10x8930 |
Additional circuit for external sensor error |
- |
0xC10x8A00 |
Actuators |
Error in external actuator. |
0xC10x8B00 |
Preventive maintenance required |
Condition monitoring. |
0xC10x8F00 |
Functional safety error |
- |
0xC10x8F01 |
Symmetry violation |
Switching sequence incorrect, discrepancy time monitoring, antivalent, equivalent). |
0xC10x8F08 |
Light test error |
Output cannot be switched on when inactive. |
0xC10x8F09 |
Dark test error |
Output cannot be switched off when active. |
0xC10x8F0F |
Inoperable state |
An I/O Module is in an inoperable state and is shut down. |
0xC10x9000 |
External error |
Errors on external devices. |
0xC10xA000 |
Sub-bus slave |
- |
0xC10xA001 |
Sub-bus slave missing |
The sub-bus master does not find the expected sub-bus slave. |
0xC10xA002 |
Incorrect sub-bus slave present |
A found sub-bus slave does not match to the intended sub-bus slave (in case that this information is stored in the sub-bus master). |
0xC10xA003 |
Compatible replacement |
The expected sub-bus slave was replaced by a compatible one. |
0xC10xA004 |
Sub-bus slaves amount error (too many slaves) |
The number of found sub-bus slaves is higher than the number of expected sub-bus slaves. |
0xC10xA010 |
Device errors |
One or more sub-bus slaves report errors. |
0xC10xA012 |
Sub-bus application not ready |
The application on the sub-bus slave is not ready. No data could be processed. |
0xC10xA013 |
Sub-bus slave reset |
The sub-bus slave was run through a reset. |
0xC10xA014 |
Sub-bus slave parameter error |
The parameterization of the sub-bus slave is missing or erroneous. |
0xC10xA020 |
Communication errors |
The basic communication of the sub-bus is not working properly (for example, caused by a baud rate error). |
0xC10xA021 |
Sub-bus error - timeout (Break) |
A timeout error was detected within the sub-bus. No telegrams where received within the timeout time by the sub-bus master. |
0xC10xA022 |
Multiple transmission error on sub-bus |
The sub-bus communication is interrupted. Too many cycles were unusable. |
0xC10xA023 |
Sub-bus I/O data communication error |
The sub-bus communication is interrupted. Too many cycles were unusable. Only data telegrams are affected. |
0xC10xA024 |
Sub-bus management data communication error |
The sub-bus communication is interrupted. Too many cycles were unusable. Only management telegrams are affected. |
0xC10xA030 |
Sub-bus configuration error |
The configuration (number or type of the sub-bus slave) does not match to the required configuration. |
0xC10xA031 |
I/O data configuration double mapped |
I/O data from two different producers is mapped to one single consumer. |
0xC10xA040 |
Common errors |
Unspecified cause. The device manual contains further information. |
0xC10xA041 |
Sub-bus hardware error |
An error of the hardware was detected. |
0xC10xA042 |
Sub-bus firmware error |
An error of the internal firmware was detected. |
0xC10xB000 |
Local bus (System bus of the modular station) |
- |
0xC10xB001 |
Local bus module missing |
- |
0xC10xB002 |
Incorrect local bus module present |
- |
0xC10xB003 |
Compatible replacement |
The expected local bus module was replaced by a compatible bus module. |
0xC10xB004 |
Local bus modules amount error (Too many modules) |
The number of found local bus modules is higher than the number of expected local bus modules. |
0xC10xB010 |
Device errors |
Error in the local bus module. |
0xC10xB012 |
Application on the local bus module not ready |
- |
0xC10xB013 |
Local bus module reset |
- |
0xC10xB014 |
Local-bus module parameterization missing or incorrect |
- |
0xC10xB020 |
Communication errors |
- |
0xC10xB021 |
Local bus error - timeout (Break) |
- |
0xC10xB022 |
Multiple transmission error on local bus |
- |
0xC10xB023 |
Local bus I/O data communication error |
- |
0xC10xB024 |
Local bus management data communication error |
- |
0xC10xB025 |
Ring topology error |
The ring topology is interrupted. |
0xC10xB030 |
Local bus configuration error |
- |
0xC10xB031 |
I/O data configuration double mapped |
- |
0xC10xB032 |
Local-bus asynchronous to superordinate system |
- |
0xC10xB040 |
Common errors |
- |
0xC10xB041 |
Local bus hardware error |
Module must be replaced. |
0xC10xB042 |
Local bus firmware error |
Module firmware or the entire module must be replaced. |
0xC10xB043 |
Local bus is running asynchronous |
In relation to the Sercos bus cycle. |
0xC10xF000 |
Additional functions |
- |