Interface of the FB_ModbusTcpServer function block:
Input |
Data type |
Description |
---|---|---|
i_xEnable |
BOOL |
Enables the Modbus TCP server. Refer to Behavior of Function blocks with the Input i_xEnable. |
i_sInterfaceIp |
STRING[15] |
Specifies the IP address of the Ethernet interface the Modbus TCP server should monitor. Enter a NULL string to monitor all Ethernet interfaces. |
i_uiServerPort |
UINT |
Specifies the TCP port the server should monitor. If the input is not assigned, the default port 502 for Modbus TCP is applied. In this case, and if the controller is an M241, M251 or M262, an error will be detected instead. |
i_uiMaxNumOfClientConnections |
UINT |
Specifies the maximum number of client connections handled by the Modbus TCP server. Default value: GCL.Gc_uiMaxNumOfClientConnectionsDefault |
i_stStartAddressConfig |
ST_StartAddressConfig |
Specifies the start addresses for the single data blocks provided by the Modbus TCP server. |
i_axAppMemoryDiscreteInputs(1) |
ARRAY OF BOOL(2) |
Specifies the data block provided as discrete inputs by the Modbus TCP server. Data can be accessed (read only) by Modbus requests using the function code |
i_axAppMemoryCoils(1) |
ARRAY OF BOOL(2) |
Specifies the data block provided as coils by the Modbus TCP server. Data can be accessed (read and write) by Modbus requests using the function codes |
i_awAppMemoryInputRegisters(1) |
ARRAY OF WORD(2) |
Specifies the data block provided as input registers by the Modbus TCP server. Data can be accessed (read only) by Modbus requests using function code |
i_awAppMemoryOutputRegisters(1) |
ARRAY OF WORD(2) |
Specifies the data block provided as holding registers by the Modbus TCP server. Data can be accessed (read and write) by Modbus requests using the function codes |
(1) These inputs are optional. For each input which is not assigned, the server handles this type of the data model as not available. (2) The specified data type is ANY. However, the documented type is the required data type which must be used for the variable assigned to this input. |
Output |
Data type |
Description |
---|---|---|
q_xActive |
BOOL |
Indicates that the function block is active. |
q_xReady |
BOOL |
Indicates that the Modbus TCP server is monitoring and incoming Modbus requests are processed. |
q_xError |
BOOL |
If this output is set to TRUE, an error has been detected. For details, refer to q_etResult and q_sResultMsg. To clear the error information, the function block must be reset. This can be achieved by disabling and re-enabling the function block. |
q_etResult |
ET_Result |
Provides diagnostic and status information as a numeric value. |
q_sResultMsg |
STRING [80] |
Provides additional diagnostic and status information as a text message. |
q_uiNumOfClients |
UINT |
Indicates the number of connected clients. |