Message MS2001: An external braking resistor is necessary.

Overview

Message ID

Message description

Message type

MS2001

An external braking resistor is necessary.

Information

Cause of the Message

Motion Sizer calculations have shown that the excess power that results from braking processes due to the configured motion and mechanics is larger than the braking power that can be consumed by the internal braking resistor.

Effect

If you designed your motion process according to the parameters you entered, the excess power could not be consumed by the internal braking resistor.

Solution

Add an external braking resistor to your application. The minimum size (in W) of the external braking resistor is indicated in the Power Circuit editor.

To reduce excess power within your application, you can also couple the internal DC buses, if this is supported by the drives you are using (for example, Lexium 32).

You can also reduce excess power by trying to optimize the motion and / or mechanics parameters of your application. Use the X Offset value of the Motion diagram, to achieve this.