ExternalBrakingResistorEnableSet

General

Type

ES

Offline editable

Yes

Devices supporting the parameter

Lexium LXM52 Drive, Lexium LXM52 Linear Drive

Traceable

No

Functional Description

This parameter determines if the internal or an external braking resistor is used.

NOTE:

Before you set this parameter to on / 1, a valid value has to be set for the following parameters:

oExternalBrakingResistorResistance

oExternalBrakingResistorContinuousPower

oExternalBrakingResistorPeakEnergy

Otherwise a detected error message occurs and the external braking resistor is not activated.

Value

Data type

Meaning

off / 0

BOOL

The internal braking resistor is used.

on / 1

BOOL

The external braking resistor is used.

NOTE: The parameter value is transferred from the master to the slave via the parameter channel of the Sercos at every access. Typically, this takes about 10 ms. However, times up to 1 s can occur if there is a lot of data transferred on the parameter channel.