RS-232, RS-422/485 Interface Description

Introduction

The HMIYMINSL series are categorized as communication modules. They are all compatible with the mini PCIe card including isolated / non-isolated RS-232, RS-422/485 communication cards for automation control.

The figure shows the RS-232, RS-422/485 interfaces:

G-SE-0038590.1.gif-high.gif

 

1   2 x RS-232, RS-422/485 interface

2   4 x RS-232, RS-422/485 interface

3   1 x interface cables

The following figure shows the dimensions of the 2 x RS-232, RS-422/485 interface:

G-SE-0038463.2.gif-high.gif

 

 

The following figure shows the dimensions of the 4 x RS-232, RS-422/485 interface:

G-SE-0038462.2.gif-high.gif

 

 

Serial Interface

The table shows technical data for the serial interfaces:

Element

Characteristics

Part number

HMIYMINSL24851

HMIYMINSL22321

HMIYMINSL44851

HMIYMINSL42321

General

Bus type

Mini PCIe card revision 1.2

Type

2 x RS-422/485, electrically isolated

2 x RS-232, electrically isolated

4 x RS-422/485, electrically non-isolated

4 x RS-232, electrically non-isolated

Connectors

2 x D-Sub 9-pin, plug

1 x D-Sub 37-pin, socket

Power consumption

3.3 Vdc at 400 mA

3.3 Vdc at 500 mA

Communication

Data bits

5, 6, 7, 8

FIFO

128 bytes

Flow control

RTS/CTS

Xon/Xoff

RTS/CTS (not supported)

Xon/Xoff

RTS/CTS

Xon/Xoff

Parity

None, odd, even, Mark and space

Speed

50 bps...921.6 kbps

50 bps...230.4 kbps

50 bps...921.6 kbps

50 bps...230.4 kbps

Stop bits

1, 1.5, 2

Transfer rate

Transfer rate

RS-232

Maximum 115 kbps with cable length ≤ 10 m

Maximum 64 kbps with cable length ≤ 15 m

Transfer rate

RS-422/485

Maximum 115 kbps with cable length ≤ 1200 m

Cable Serial Interface

The table shows the technical data of the cable serial interface:

Element

Characteristics

Signal lines

Cable cross section RS-232

Cable cross section RS-422

Cable cross section RS-485

Wire insulation

Conductor resistance

Stranding

Shield

4 x 0.16 mm² (26 AWG), tinned Cu. wire

4 x 0.25 mm² (24 AWG), tinned Cu. wire

4 x 0.25 mm² (24 AWG), tinned Cu. wire

Protective earth ground

≤ 82 Ω/km

Wires stranded in pairs

Paired shield with aluminum foil

Grounding line

Cable cross section

Wire insulation

Conductor resistance

1 x 0.34 mm² (22 AWG/19), tinned Cu. wire

Protective earth ground

≤ 59 Ω/km

Outer sheathing

Material

Features

Cable shielding

PUR mixture

Halogen free

From tinned Cu. wires

Serial Interface Connections

This interface is used to connect the S-Panel PC to remote equipment, via a cable. The connector is a D-Sub 9-pin plug connector.

By using a long PLC cable to connect to the S-Panel PC, it is possible that the cable can be at an electrical potential that is different from the electrical potential of the panel, even if both are connected to ground.

The serial port that is not isolated has the signal ground (SG) and the functional ground terminals connected inside the panel.

DangerElectrical_Color.gifDanger_Color.gifDANGER

ELECTRIC SHOCK

oMake a direct connection between the ground connection screw and ground.

oDo not connect other devices to ground through the ground connection screw of this device.

oInstall all cables according to local codes and requirements. If local codes do not require grounding, follow a reliable guide such as the US National Electrical Code, Article 800.

Failure to follow these instructions will result in death or serious injury.

The table shows the D-Sub 9-pin assignments:

Pin

Assignment

RS-232

RS-422/485

 

1

DCD

TxD-/Data-

D-Sub 9-pin plug connector:

G-SE-0009066.2.gif-high.gif

 

 

2

RxD

TxD+/Data+

3

TxD

RxD+

4

DTR

RxD-

5

GND

GND/VEE

6

DSR

RTS-

7

RTS

RTS+

8

CTS

CTS+

9

RI

CTS-

The table shows the D-Sub 37-pin assignments:

Pin

Assignment

RS-232

RS-422/485

 

1

N.C.

N.C.

D-Sub 37-pin socket connector:

G-SE-0038758.1.gif-high.gif

 

 

2

DCD3

TxD3-/Data3-

3

GND

GND/VEE3

4

CTS3

N.C.

5

RxD3

TxD3/Data3

6

RI4

N.C.

7

DTR4

RxD4-

8

DSR4

N.C.

9

RTS4

N.C.

10

TxD4

RxD4

11

DCD2

TxD2-/Data2-

12

GND

GND

13

CTS2

N.C.

14

RxD2

TxD2/Data2

15

RI1

N.C.

16

DTR1

RxD1-

17

DSR1

N.C.

18

RTS1

N.C.

19

TxD1

RxD1

20

RI3

N.C.

21

DTR3

RxD3-

22

DSR3

N.C.

23

RTS3

N.C.

24

TxD3

RXD3

25

DCD4

TxD4-/Data4-

26

GND

GND/VEE4

27

CTS4

N.C.

28

RxD4

TxD4/Data4+

29

RI2

N.C.

30

DTR2

RxD2-

31

DSR2

N.C.

 

32

RTS2

N.C.

33

TxD2

RxD2

34

DCD1

TxD1-/Data1-

35

GND

GND/VEE1

36

CTS1

N.C.

37

RxD1

TxD1/Data1+

Any excessive weight or stress on communication cables may disconnect the equipment.

Caution_Color.gifCAUTION

LOSS OF POWER

oEnsure that communication connections do not place excessive stress on the communication ports of the Magelis Industrial PC.

oSecurely attach communication cables to the panel or cabinet.

oUse only D-Sub 9-pin cables with a locking system in good condition.

Failure to follow these instructions can result in injury or equipment damage.

RS-485 Interface Specificity

NOTE: All the pins of the RS-422 default interface should be used for operation.

The RTS line must be switched each time the driver is sent and received. There is no automatic switch back. This cannot be configured in Windows.

The voltage drop caused by long line lengths can lead to greater potential differences between bus stations, which can hinder communication. You can improve the communication by running a ground wire with the other wires.

NOTE: When using RS-422/485 communication with PLCs, you may need to reduce the transmission speed and increase the TX Wait time.

Compatible Table

Part number

Description

S-Panel PC

HMIYMINSL24851

Inteface 2 x RS-422/485 isolation

Yes

HMIYMINSL44851

Inteface 4 x RS-422/485 isolation, DB37, cable

Yes

HMIYMINSL22321

Inteface 2 x RS-232 isolation

Yes

HMIYMINSL42321

Inteface 4 x RS-232, DB 37, cable

Yes

Cable Routing

S-Panel PC and HMIYMINSL42321:

G-SE-0063647.1.gif-high.gif

 

 

S-Panel PC and HMIYMINSL22321:

G-SE-0063652.1.gif-high.gif

 

 

S-Panel PC and HMIYMINSL44851:

G-SE-0063646.1.gif-high.gif

 

 

S-Panel PC and HMIYMINSL24851:

G-SE-0063651.1.gif-high.gif

 

 

Device Manager and Hardware Installation

Install the driver before you install the interface into the S-Panel PC. The driver installation media is included with the package. After the interface is installed, you can verify whether it is properly installed on your system through the Device Manager.