Installing onto Display Module
NOTICE |
EQUIPMENT DAMAGE |
oWhen mounting this product vertically, before attaching to the panel, install the Box Module onto the Display Module. oWhen installing the Box Module onto the Display Module, place the Display Module on a clean and level surface with the screen facing downward. |
Failure to follow these instructions can result in equipment damage. |
Step |
Action |
---|---|
1 |
Pull the LOCK forward on the top of the Box Module to release the lock as illustrated.
1 LOCK |
2 |
Insert the protruding points on the bottom left and right of the Box Module into the two holes on the back of the Display Module to attach the Box Module.
2 Protruding points 3 Box Module 4 Holes for insertion 5 Display Module |
3 |
Fully push on the LOCK on the top of the Box Module to mount the Box Module on the Display Module
1 LOCK |
NOTE: For instructions on how to mount the Display Module to the panel, refer to Installing to the Panel.