Overview
The following table contains leakage current per device:
Application
|
Per power supply
|
For each drive module
|
Typical (400 V, 50 Hz)
|
≤ 141 mA
|
≤ 9 mA
|
NOTE: If the leakage current is too high for the respective application, use an isolating transformer on the mains supply.
This product has a leakage current greater than 3.5 mA. If the protective ground connection is interrupted, a hazardous touch current may flow if the housing is touched.
DANGER
|
|
INSUFFICIENT GROUNDING
-
Use a protective ground copper conductor with at least 10 mm2 (AWG 6) or two protective ground copper conductors with the same or larger cross section of the conductors supplying the power terminals.
-
Verify compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to grounding of all equipment.
Failure to follow these instructions will result in death or serious injury.
|