Observe the following instructions before carrying out maintenance on the Lexium 62 Drive System.
DANGER | |
---|---|
How to de-energize the system:
Step |
Action |
---|---|
1 |
Set main switch to OFF position, or otherwise disconnect all power to the system. |
2 |
Prevent main switch from being switched back on. |
3 |
In the case of any drives, servos or other equipment with high capacity capacitors, wait at least 15 minutes after removing power (switching off) to allow the DC bus capacitors to discharge. |
4 |
Verify whether the DC-BUS LED indicator has turned off on all components located in the axis group. |
5 |
Verify with an appropriate measuring instrument that the voltages between DC+ to PE (Protective Earth/ground), DC- to PE and DC+ to DC- are all less than 42.4 Vdc. |
DANGER | |
---|---|
For further information on the DC Bus LED indicator, refer to Bus Bar Module LED Indicators on the Lexium 62 Power Supply and Lexium 62 Servo Drive.