Prerequisites for Replacing Components and Cables

De-Energize the System

 DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
  • Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires.
  • Place a "Do Not Turn On" or equivalent hazard label on all power switches and lock them in the non-energized position.
  • Wait 15 minutes to allow the residual energy of the DC bus capacitors to discharge.
  • Measure the voltage on the DC bus with a properly rated voltage sensing device and verify that the voltage is less than 42.4 Vdc.
  • Do not assume that the DC bus is voltage-free when the DC bus LED is off.
  • Block the motor shaft to prevent rotation prior to performing any type of work on the drive system.
  • Do not create a short-circuit across the DC bus terminals or the DC bus capacitors.
  • Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
  • Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.

How to de-energize the system:

Step

Action

1

Set main switch to OFF position, or otherwise disconnect all power to the system.

2

Prevent main switch from being switched back on.

3

In the case of any drives, servos or other equipment with high capacity capacitors, wait at least 15 minutes after removing power (switching off) to allow the DC bus capacitors to discharge.

4

Verify whether the DC-BUS LED indicator has turned off on all components located in the axis group.

5

Verify with an appropriate measuring instrument that the voltages between DC+ to PE (Protective Earth/ground), DC- to PE and DC+ to DC- are all less than 42.4 Vdc.

 DANGER
ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Verify with a correctly calibrated measuring instrument that the DC bus is de-energized (less than 42.4 Vdc) before replacing, maintaining or cleaning machine components.
Failure to follow these instructions will result in death or serious injury.

For further information on the DC Bus LED indicator, refer to Bus Bar Module LED Indicators on the Lexium 62 Power Supply and Lexium 62 Servo Drive.

Other Prerequisites

 DANGER
ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
  • Operate electrical components only with a connected protective ground (earth) cable.
  • After the installation, verify the secure connection of the protective ground (earth) cable to all electrical devices to ensure that connection complies with the connection diagram.
  • Before enabling the device, safely cover the live components to prevent contact.
  • Do not touch the electrical connection points of the components when the module is energized.
  • Provide protection against indirect contact.
  • Connect and disconnect cables and terminals only after you have verified that the power has been removed from the system.
  • Insulate the unused conductors on both ends of the motor cable.
Failure to follow these instructions will result in death or serious injury.

There are no user-serviceable parts within the Lexium 62 components. Either replace the entire drive or contact your Schneider Electric representative.

 WARNING
UNINTENDED EQUIPMENT OPERATION
  • Only use software and hardware components approved by Schneider Electric for use with this equipment.
  • Do not attempt to service this equipment outside of authorized Schneider Electric service centers.
  • Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
 WARNING
IMPROPER REPLACEMENT OR OPENING OF THE COMPONENT HOUSING
  • Do not open the housing of the components for commissioning, replacement, or any other reason whatsoever unless otherwise instructed in the specific product documentation of the component.
  • Observe and respect the instructions and specifications contained in the product documentation and that of the machine manufacturer when replacing components.
  • Replace inoperable components as a whole.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

The metal surfaces of the product may exceed 65 °C (149 °F) (for bare metal) during operation.

 WARNING
HOT SURFACES
  • Avoid unprotected contact with hot surfaces.
  • Do not allow flammable or heat-sensitive parts in the immediate vicinity of hot surfaces.
  • Verify that the heat dissipation is sufficient by performing a test run under maximum load conditions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.