Presentation

When replacing Lexium 62 components, be sure to observe the important safety information in the sections of the present document concerning mounting and dismounting components.

 DANGER
ELECTRIC SHOCK CAUSED BY HIGH LEAKAGE (TOUCH) VOLTAGE
  • Before working on the product, make sure that it is de-energized.
  • After disconnection, do not touch connector CN6 mains connection on the Lexium 62 Power Supply module as it still carries hazardous voltages for approximately one second.
  • Only operate the Lexium 62 components in a control cabinet that cannot be opened without the help of tools.
Failure to follow these instructions will result in death or serious injury.

There are no user-serviceable parts within the Lexium 62 components. Either replace the entire drive or contact your Schneider Electric representative.

 WARNING
UNINTENDED EQUIPMENT OPERATION
  • Only use software and hardware components approved by Schneider Electric for use with this equipment.
  • Do not attempt to service this equipment outside of authorized Schneider Electric service centers.
  • Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Use only the accessories and mounting parts specified in the documentation and no third-party devices or components that have not been expressly approved by Schneider Electric. Do not modify the equipment.

In case machine repair includes the replacement of the drive components, observe the following instructions for ESD protection in order to avoid any damage due to electrostatic discharge:

NOTICE
ELECTROSTATIC DISCHARGE
  • Do not touch any of the electrical connections or components.
  • Prevent electrostatic charges, for example, by wearing appropriate clothing.
  • If you must touch circuit boards, do so only on the edges.
  • Remove existing static charge by touching a grounded, metallic surface.
Failure to follow these instructions can result in equipment damage.