To add a Modbus IOScanner on a Serial Line, select the in the , drag it to the , and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
To configure a Modbus IOScanner on a Serial Line, double-click in the .
The configuration window is displayed as below:
Set the parameters as described in this table:
|
Element |
Description |
|---|---|
|
|
Specifies the transmission mode to use:
Set this parameter identical for each Modbus device on the network. |
|
|
Timeout used in the exchanges. |
|
|
Delay to reduce data collision on the bus. Set this parameter identical for each Modbus device on the network. |
The Modbus IOScanner and the devices exchange data at each cycle of the chosen application task.
To select this task, select the tab. The configuration window is displayed as below:
The parameter allows you to select the application task that manages the scanner:
: associate the scanner with the application task that manages the controller.
: associate the scanner with the MAST task.
Another existing task: you can select an existing task and associate it to the scanner. For more information about the application tasks, refer to the EcoStruxure Machine Expert - Programming Guide.
The scan time of the task associated with the scanner must be less than 500 ms.