OPC UA Server Configuration

Introduction

The OPC UA Server Configuration window allows you to configure the OPC UA server. OPC UA server is using encrypted communication by default with maximum security settings set by default.

Accessing the OPC UA Server Configuration Tab

To configure the OPC UA Server:

Step

Action

1

In the Devices tree, double-click MyController.

2

Select the OPC UA Server Configuration tab.

OPC UA Server Configuration Tab

The following figure shows the OPC UA Server Configuration window:

OPC UA Server Configuration Description

This table describes the OPC UA Server Configuration parameters:

General Settings

Parameter

Value

Default value

Description

OPC UA Server Enabled

Enabled/ Disabled

Disabled

This checkbox is used to enable or disable the OPC UA Server and Client on the controller.

Security Settings

Parameter

Value

Default value

Description

Disable anonymous login

Enabled/ Disabled

Enabled

Uncheck this checkbox to allow anonymous login on OPC UA server.

Security Policy

None

Basic256(deprecated) (1)

Basic256Sha256

Basic256Sha256

This drop-down menu allows you to secure your exchanges by signing and encrypting the data you send and receive.

Message Security

None

Sign

SignAndEncrypt

SignAndEncrypt

The messages are related to the Security Policy selected.

(1) Security policies marked as deprecated are policies which no longer afford an acceptable level of security.

Server Configuration

Parameter

Value

Default value

Description

Server port

1...65535

4840

The port number of the OPC UA server. OPC UA clients must append this port number to the TCP URL of the controller to connect to the OPC UA server.

Max. subscriptions per session

1...100 (2)

20

Specify the maximum number of subscriptions allowed within each session.

Min. publishing interval

200...5000

1000

The publishing interval defines how frequently the OPC UA server sends notification packages to clients. Specify the minimum time that must elapse between notifications, in ms.

Max. monitored items per subscription

1...10000 (2)

100

The maximum number of monitored items in each subscription that the server assembles into a notification package.

Min. KeepAlive interval

500...5000

500

The OPC UA server only sends notifications when the values of monitored items of data are modified. A KeepAlive notification is an empty notification sent by the server to inform the client that although no data has been modified, the subscription is still active. Specify the minimum interval between KeepAlive notifications, in ms.

Max. number of sessions

1...4

2

The maximum number of clients that can connect simultaneously to the OPC UA server.

Identifier type

String

String

Certain OPC UA clients require a specific format of unique symbol identifier (node ID).

(2) The total count (Max. subscriptions per session x Max. monitored items per subscription) cannot exceed 10000.

Diagnostic

Parameter

Value

Default value

Description

Enable trace

Enabled/disabled

Enabled

Select this checkbox to include OPC UA diagnostic messages in the controller log file. Traces are available from the Log tab or from the System Log File of the Web server.

You can select the category of events to write to the log file:

  • None

  • Error

  • Warning

  • System

  • Info

  • Debug

  • Content

  • All (default)

Sampling rates (ms)

200...5000

500

1000

2000

The sampling rate indicates a time interval, in milliseconds (ms). When this interval has elapsed, the server sends the notification package to the client. The sampling rate can be shorter than the publishing interval, in which case notifications are queued until the publishing interval has elapsed.

Sampling rates must be in the range 200...5000 (ms).

Up to 3 different sampling rates can be configured.

Double-click on a sampling rate to edit its value.

To add a sampling rate to the list, right-click and choose Add a new rate.

To remove a sample rate from the list, select the value and click .

Click Reset to default to return the configuration parameters on this window to their default values.

Client Certificate Management Tab

This tab allows you to determine which OPC UA client certificates are trusted by the M262 Logic/Motion Controller OPC UA server.

Client Certificate Management Tab, Toolbar

Element

Description

Both certificate lists are loaded or refreshed.

Deletes the selected certificates.

Opens a Windows dialog box (Open) to import a certificate that is uploaded to the selected certificate list (trusted certificates list or rejected certificates list).

Opens a Windows dialog box (Save as) to export the selected certificates to a selectable path.

Opens a dialog box containing additional information on the selected certificate.

Trusted Certificates List and Rejected Certificates List

A certificate contains common information about the company that owns the certificate, how long a certificate is valid, and so on. The certificate management provides two list views:
  • trusted certificates

  • rejected certificates.

Element

Description

Trusted certificates

This list includes the client certificates the server trusts.

Rejected certificated

This list includes the client certificates the server does not trust.

Use the << and >> buttons to move a rejected certificate to the Trusted certificates list or the opposite way.

During the moving procedure, a progress bar appears and displays the remaining files.

NOTE: OPC UA client and server share the same default PKI folder structure, including the trusted and untrusted (rejected) folders, this means trusting or untrusting (rejecting) a certificate has the same effect for both client and server.
NOTE: The OPC UA self-signed certificate has a limitation when the network interface through which OPC UA communicates is using dynamic IP addresses (DHCP). If you configured DHCP in such interface, make sure your OPC UA peer accepts the M262 Logic/Motion Controller OPC UA self-signed certificate without validation.

OPC UA Certificates Management Actions

This table describes each action concerning OPC UA certificates management and how to achieve it.

Action / Task

EcoStruxure Machine Expert

Security Screen (1)

EcoStruxure Machine Expert

M262 Files Screen (2)

EcoStruxure Machine Expert

M262 OPC UA Server Screen (3)

M262 Webpage

Maintenance - Certificates

FTP

Protocol (2)

Access to M262 OPC UA PKI folders

YES

YES

YES

NO

YES

Import a certificate

YES

YES

YES

NO

YES

Export a Certificate

YES

YES

YES

NO

YES

Remove a certificate

YES

YES

YES

NO

YES

Trust / Untrust a certificate

NO

YES (4)

YES

YES (5)

YES (4)

Check a certificate information

YES

NO

YES

NO

NO

PKI: Public Key Infrastructure.

(1) Only for M262 own certificates folder.

(2) Except M262 own certificates folder.

(3) Only trusted and untrusted (rejected) certificate folders.

(4) Requires to manually move the certificate from the trusted folder to the untrusted (rejected) folder (and vice-versa).

(5) Requires Administrator access.

OPC UA PKI Folder List and Usage

The table describes the Public Key Infrastructure (PKI) shared between the M262 Logic/Motion Controller OPC UA server and OPC UA Client. It provides the folder list and their usage.

M262 File System Folders

Description

/usr/pki

Root folder of the default PKI

/usr/pki/issuer/certs

Contains Certificate Authority (CA) certificates that are required to validate Certification Paths

/usr/pki/issuer/crl

Contains Certificate Revocation Lists (CRL) for CA certificates

/usr/pki/trusted/certs

Contains Trusted certificates

/usr/pki/trusted/crl

Contains Certificate Revocation Lists (CRL) for the Trusted certificates

/usr/pki/untrusted

Contains Untrusted certificates

/usr/pki/quarantine

not used for M262 OPC UA (legacy for other services)

NOTE: Some of the PKI folders are only available after downloading the application enabling OPC UA (server/client), since some folders are only created in the runtime initialization of OPC UA.