Overview
This section describes the wiring guidelines and associated best practices to be respected when using the TM3 system.
|
DANGER
|
|
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
-
Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
-
Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
-
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
-
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
|
|
WARNING
|
|
LOSS OF CONTROL
-
Perform a Failure Mode and Effects Analysis (FMEA), or equivalent risk analysis, of your application, and apply preventive and detective controls before implementation.
-
Provide a fallback state for undesired control events or sequences.
-
Provide separate or redundant control paths wherever required.
-
Supply appropriate parameters, particularly for limits.
-
Review the implications of transmission delays and take actions to mitigate them.
-
Review the implications of communication link interruptions and take actions to mitigate them.
-
Provide independent paths for control functions (for example, emergency stop, over-limit conditions, and error conditions) according to your risk assessment, and applicable codes and regulations.
-
Apply local accident prevention and safety regulations and guidelines.1
-
Test each implementation of a system for proper operation before placing it into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
1 For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems or their equivalent governing your particular location.
Wiring Guidelines
The following rules must be applied when wiring a TM3 system:
-
I/O and communication wiring must be kept separate from the power wiring. Route these 2 types of wiring in separate cable ducting.
-
Verify that the operating conditions and environment are within the specification values.
-
Use proper wire sizes to meet voltage and current requirements.
-
Use minimum 60 °C (140 °F) copper conductors for TM3XTYS4.
-
Use minimum 90 °C (194 °F) copper conductors for TM3X•HSC202•.
-
Use twisted-pair, shielded cables for analog, and/or fast I/O.
-
Use twisted-pair, shielded cables for networks, and field bus.
|
WARNING
|
|
UNINTENDED EQUIPMENT OPERATION
-
Use shielded cables for all fast I/O, analog I/O, and communication signals.
-
Ground cable shields for all fast I/O, analog I/O, and communication signals at a single point1.
-
Route communications and I/O cables separately from power cables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
1Multipoint grounding is permissible if connections are made to an equipotential ground plane dimensioned to help avoid cable shield damage in the event of power system short-circuit currents.
NOTE: Surface temperatures may exceed 60 °C (140 °F).
To conform to IEC 61010 standards, route primary wiring (wires connected to power mains) separately and apart from secondary wiring (extra low voltage wiring coming from intervening power sources). If that is not possible, double insulation is required such as conduit or cable gains.
Rules for Removable Screw Terminal Block
The following tables show the cable types and wire sizes for a 3.81 pitch removable screw terminal block (I/Os and power supply):
The following tables show the cable types and wire sizes for a 5.08 pitch removable screw terminal block (I/Os and power supply):
The use of copper conductors is required.
|
DANGER
|
|
FIRE HAZARD
-
Use only the correct wire sizes for the maximum current capacity of the I/O channels and power supplies.
-
For relay output (2 A) wiring, use conductors of at least 0.5 mm2 (AWG 20) with a temperature rating of at least 80 °C (176 °F).
-
For common conductors of relay output wiring (7 A), or relay output wiring greater than 2 A, use conductors of at least 1.0 mm2 (AWG 16) with a temperature rating of at least 80 °C (176 °F).
Failure to follow these instructions will result in death or serious injury.
|
Rules for Removable Spring Terminal Block
The following tables show the cable types and wire sizes for a 3.81 pitch removable spring terminal block (I/Os and power supply):
The following tables show the cable types and wire sizes for a 5.08 pitch removable spring terminal block (I/Os and power supply):
The use of copper conductors is required.
|
DANGER
|
|
FIRE HAZARD
-
Use only the correct wire sizes for the maximum current capacity of the I/O channels and power supplies.
-
For relay output (2 A) wiring, use conductors of at least 0.5 mm2 (AWG 20) with a temperature rating of at least 80 °C (176 °F).
-
For common conductors of relay output wiring (7 A), or relay output wiring greater than 2 A, use conductors of at least 1.0 mm2 (AWG 16) with a temperature rating of at least 80 °C (176 °F).
Failure to follow these instructions will result in death or serious injury.
|
The spring clamp connectors of the terminal block are designed for only one wire or one cable end. Two wires to the same connector must be installed with a double wire cable end to help prevent loosening.
|
DANGER
|
|
LOOSE WIRING CAUSES ELECTRIC SHOCK
Do not insert more than one wire per connector of the spring terminal blocks unless using a double wire cable end (ferrule).
Failure to follow these instructions will result in death or serious injury.
|
Protecting Outputs from Inductive Load Damage
Depending on the load, a protection circuit may be needed for the outputs on the controllers and certain modules. Inductive loads using DC voltages may create voltage reflections resulting in overshoot that will damage or shorten the life of output devices.
|
CAUTION
|
|
OUTPUT CIRCUIT DAMAGE DUE TO INDUCTIVE LOADS
Use an appropriate external protective circuit or device to reduce the risk of inductive direct current load damage.
Failure to follow these instructions can result in injury or equipment damage.
|
If your controller or module contains relay outputs, these types of outputs can support up to 240 Vac. Inductive damage to these types of outputs can result in welded contacts and loss of control. Each inductive load must include a protection device such as a peak limiter, RC circuit or flyback diode. Capacitive loads are not supported by these relays.
|
WARNING
|
|
RELAY OUTPUTS WELDED CLOSED
-
Always protect relay outputs from inductive alternating current load damage using an appropriate external protective circuit or device.
-
Do not connect relay outputs to capacitive loads.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
AC-driven contactor coils are, under certain circumstances, inductive loads that generate pronounced high-frequency interference and electrical transients when the contactor coil is de-energized. This interference may cause the logic controller to detect an I/O bus error.
|
WARNING
|
|
CONSEQUENTIAL LOSS OF CONTROL
Install an RC surge suppressor or similar means, such as an interposing relay, on each TM3 expansion module relay output when connecting to AC-driven contactors or other forms of inductive loads.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
Protective circuit A: this protection circuit can be used for both AC and DC load power circuits.
C Value from 0.1 to 1 μF
R Resistor of approximately the same resistance value as the load
Protective circuit B: this protection circuit can be used for DC load power circuits.
Use a diode with the following ratings:
Protective circuit C: this protection circuit can be used for both AC and DC load power circuits.
In applications where the inductive load is switched on and off frequently and/or rapidly, ensure that the continuous energy rating (J) of the varistor exceeds the peak load energy by 20 % or more.