The red SE LED indicator makes it possible to evaluate the following error states:
Detected internal module error (hardware error)
Over/under temperature
Over/under voltage
Incompatible firmware version
The wiring issues described in the section Connection Examples are detected using the red I/O channel LED indicator.
After an error within the module is detected, the module reverts back to a defined safe state.
Recognizable errors are detected by the module within the error detection time.
If a module detects an error, then:
The channel LED indicator is lit constantly red
The SafeChannelOKxx
signal is set to SAFEFALSE
.
The SafeDigitalInputxx
or SafeDigitalOutputxx
signal is set to SAFEFALSE
.
An entry is generated in the Safelogger of EcoStruxure Machine Expert.
For more information on wiring errors, refer to Connection Examples.
Other errors that are not detected by the module (or not detected on time) may lead to unintended machine states and therefore must be uncovered using additional measures.
WARNING | |
---|---|
For more information on errors that are, and are not, detected by the Safety I/O module, refer to the table for error detection in the Connection Examples hereafter.
Make all necessary repairs in a timely manner if an error occurs because subsequent errors could create a hazardous situation.
WARNING | |
---|---|