TM5SPS1

Introduction

The TM5SPS1 expansion electronic module is a 24 Vdc power supply electronic module for internal I/O supply.

TM5 Module I/O Mapping Tab

Variables can be defined and named in the TM5 Module I/O Mapping tab. Additional information such as topological addressing is also provided in this tab.

Refer Status Mapping, for the status bits configuration details.

For further generic descriptions, refer to TM5 Module I/O Mapping Tab Description.

Status Bit Mapping

This table describes the TM5SPS1 status bit mapping configuration:

Channel

Type

Description

ModuleOK

BYTE

State of the compact I/O and electronic modules

DcOk

BOOL

Voltage range:

  • 0: Invalid

  • 1: Valid

reserved

BOOL

Reserved

NetworkOk

BOOL

TM5 bus:

  • 0: Bus error

  • 1: OK

I/O Data valid

BOOL

Data validity:

  • 0: Valid

  • 1: Invalid

reserved

BOOL

Reserved

reserved

BOOL

Reserved

reserved

BOOL

Reserved

reserved

BOOL

Reserved

Status

BYTE

Status of the module

Bus power supply warning

BOOL

Bus power supply status:

  • 0 = OK
  • 1 = low voltage < 4.7 V

reserved

BOOL

Not used (bit = 0)

I/O power supply warning

BOOL

I/O power supply status:

  • 0 = OK
  • 1 = I/O power supply < 20.4 V

User-Defined Parameters Tab

There is no user configuration for this module.