TM7BAO4CLA Presentation

Main Characteristics

The table below provides the main characteristics of the TM7BAO4CLA block:

Main characteristics

Number of output channels

4

Signal type

Current

Output range

0...20 mA

Resolution

12 bits

Actuator connection type

M12, A coded, female connector type

Description

The following figure shows the TM7BAO4CLA block:

G-SE-0006514.1.gif

 

(A)   TM7 bus IN connector

(B)   TM7 bus OUT connector

(C)   24 Vdc power IN connector

(D)   24 Vdc power OUT connector

(1)   Output connectors

(2)   Status LEDs

Connector and Channel Assignments

The table below provides the connector and channel assignments of the TM7BAO4CLA block:

Output connectors

Output status LEDs

Channel type

Channels

1

1

Output

Q0

2

2

Output

Q1

3

3

Output

Q2

4

4

Output

Q3

Status LEDs

The following figure shows the status LEDs of the TM7BAO4CLA block:

G-SE-0006368.1.gif

 

(1)   TM7 bus status LEDs, set of two LEDs: 1.1 (green) and 1.2 (red)

(2)   Output status LEDs, composed of four LEDs: 1, 2, 3 and 4 (yellow)

(3)   Output block status LEDs, set of two LEDs: 3.1 (green) and 3.2 (red)

The table below provides the TM7 bus status LEDs of the TM7BAO4CLA block:

TM7 bus status LEDs

Description

LED 1.1

LED 1.2

OFF

OFF

No power supply on TM7 bus

ON

ON

TM7 bus in preoperational state:

opower supply on TM7 bus and

oblock not initialized

ON

OFF

TM7 bus in operational state

OFF

ON

TM7 bus error detected

The table below provides the output status LEDs of the TM7BAO4CLA block:

Channel LEDs

State

Description

1 - 4

OFF

Open connection or actuator is disconnected

ON

The analog/digital converter is running, a value is available

The table below provides the output block status LEDs of the TM7BAO4CLA block:

Block status LEDs

State

Description

3.1

OFF

No power supply

Single Flash

Reset state

Flashing

Preoperational state

ON

Operational state

3.2

OFF

OK or no power supply

Double Flash

Power supply not in the valid range

ON

Detected error or reset state